Wiring Guide
Using Netbell Ultra 300 with Bogen PCM2000
How to wire a Netbell Ultra 300 output to the emergency/shift-change trigger on a Bogen PCM2000 paging system, so the Netbell schedule can start the PCM2000’s signal.
01How It Works
The Bogen PCM2000 central processor (PCMCPU) has an EMSC (emergency/shift-change) trigger input. When EMSC is connected to GND, the PCM2000 starts the signal that is programmed for that input.
Wire output OUT2 on the Netbell Ultra 300 across EMSC and GND. Each time the Netbell schedule activates OUT2, its relay closes and the PCM2000 starts the signal.
OUT2 is a dry relay contact, so the two wires have no polarity. Either wire can go to either OUT2 terminal.
Set up the emergency/shift-change signal in the PCM2000 itself. See the Bogen PCM2000 manual for how to program it.
02Wire the Ultra 300 to the PCM2000
- Turn off power to the Netbell Ultra 300 and the PCM2000.
- On the PCMCPU terminal block, find the GND and EMSC terminals. They are next to each other, after the AUX terminal.
- Connect GND to the C (common) terminal of OUT2 on the Ultra 300.
- Connect EMSC to the NO (normally open) terminal of OUT2.
- Turn the power back on, then test by activating OUT2 from the Netbell web pages.