User Manual
Ultra 300 Ethernet I/O Controller
Wiring, network access, web interface, hour meter and bell features, automated tasks, settings and data collection for the Ultra 300 controller in all its software versions.
01Overview
The Ultra 300 is a compact Ethernet I/O controller with 2 relay outputs, 2 digital inputs, 2 analog inputs, a voltage output, an on-board temperature sensor and accelerometer, and a port for an optional temperature/humidity sensor. It is referred to as the SERVER throughout this manual.
The Ultra 300 ships with one of several software versions. Most of this manual applies to all of them; sections that apply to one version only are marked:
| Software | Extra features | See |
|---|---|---|
| Standard I/O | Relay and input control, tasks, logs, remote devices, MQTT and RESTful access. | All sections except those marked below |
| Hour Meter (iTrixx) | Up to 16 independent hour meters with their own landing page, email and relay alerts, and data collection apps. | Activate the Meter, Hour Meter, Data Collection |
| Bell (Netbell) | Bell events and schedules, plus 2 virtual relays for extra slave controllers. | 4 Relays, Bells and Schedules |
02Wiring the Server
Board Layout Reference
| # | Item | Details |
|---|---|---|
| 1 | Relay outputs | 2 signal relays, 1 Form C, 1 A @ 30 VDC. Relay 2 is on the left. |
| 2 | Voltage output | Powers external devices such as a sensor. The voltage depends on how the SERVER is powered (see Voltage Output). |
| 3 | Digital inputs | 2 inputs, 5–48 VDC (24–48 VDC requires the external resistor). Input 2 is on the left. |
| 4 | Analog inputs | 2 inputs. Input 2 is on the left. |
| 5 | CAN inputs | Not yet supported by the software. |
| 6 | Digital input switches | One per input, IN2 on the left. Up = Pull-up (PU), down = Isolated (ISO). |
| 7 | RESET button | Restarts the SERVER (see Reset to Factory Default). |
| 8 | RELOAD button | Restores factory defaults when used with RESET. |
| 9 | RJ45 connector | Ethernet network and PoE. |
| 10 | USB mini connector | For the AM2302 temperature/humidity sensor (sold separately). |
| 11 | Power input | Micro-USB, marked POWER; 5–24 VDC. |
These units are ground-isolated. Connect so the power loop is connected only to the SERVER, and do not use external ground connections. Doing so may damage the SERVER or the PoE source device.
Power Connection
The power input is a micro-USB connector marked POWER on the enclosure. Power the SERVER in one of three ways:
- Power supply: plug the 12 VDC power supply into an AC outlet and its cable into the POWER connector.
- Computer: connect the POWER connector to a computer with a USB cable. This also lets you read the IP address over USB.
- PoE: connect the RJ45 connector to a PoE network switch.
When using a PoE switch, do not also connect the 12 VDC power supply. It will damage the board.
| LED | Meaning |
|---|---|
| Green (Boot) flashing | Bootload mode, right after power-on. In this mode the server software can be updated. |
| Red blinking once per second | After about 5 seconds the green LED goes off: Server mode. The SERVER is reachable on the network over TCP/IP. |
Network Connection
Plug an Ethernet cable into the RJ45 (NET) connector. The Connection LED on the connector comes on when it is connected to a switch with a 100 Mbps network; the Activity LED blinks to show network activity.
Relay Connections
The SERVER has 2 signal relays (1 Form C, 1 A @ 30 VDC) with push-in spring connectors, numbered OUT 1 and OUT 2. They are dry-contact relays designed for low-voltage control only: never apply more than 30 V to a relay, for your safety and to stay within the ratings of the board.
Each relay has three terminals: NO (Normally Open), C (Common) and NC (Normally Closed). When the relay activates, the connection moves from C–NC to C–NO.
- To make a connection when the relay activates, wire between C and NO.
- To break a circuit when the relay activates, wire between C and NC.
Voltage Output
The voltage output can power external devices, such as a sensor or an external relay. Its voltage depends on how the SERVER is powered, minus a small voltage drop:
| SERVER powered by | Voltage output |
|---|---|
| USB | 5 V |
| PoE | 12 V |
| External power supply | Same as the supply voltage |
The output is limited to 50 mA. Wire the positive side of the external device to the Voltage/+ terminal and, if needed, the negative side to GND.
Digital Input Connections
The two digital inputs, labeled IN1 and IN2, use push-in spring connectors. Each has two terminals: C (cathode, −) and A (anode, +).
Digital inputs detect the on/off state of an external sensor. The SERVER can show whether an input is on or off, count events (resettable or non-resettable counter), and calculate frequency (for example, as a tachometer) or period.
Each input has two modes, selected by its switch (see Board Layout Reference): down for ISO (isolated), up for PU (pull-up). They are set to ISO at the factory.
| Mode | How it works |
|---|---|
| PULL UP | Connects a 1 kΩ resistor to an internal voltage, so you can use a simple switch (such as a magnetic door switch) across the two terminals. When the switch is activated, a signal is sent to the input. |
| ISOLATED | You drive the opto-isolator directly with an external voltage through an internal 1 kΩ resistor. The voltage can be 5–24 V, supplying a minimum of 2 mA and a maximum of 30 mA. There is no other internal connection to this voltage. |
If you use isolated mode, check the switch is set to ISO before applying an external voltage. Otherwise you may damage the SERVER or the PoE source device.
Analog Input Connections
Analog inputs read values from external equipment such as temperature or pressure sensors. The two inputs, labeled AN1 and AN2, use push-in spring connectors with one terminal each and accept 0–5 V sensors. The SERVER provides ground and power connections, so no external voltage reference is needed.
- 2-wire sensor: data wire to the analog input (and to a power source if needed), ground wire to GND.
- 3-wire sensor: data wire to the analog input, ground wire to GND, power wire to Voltage/+.
The analog inputs are not isolated. Use an isolated sensor that makes no connection to a remote ground.
Activate the Meter (Hour Meter Software)
The hour meter software has up to 16 separate hour counters, each with its own trigger. Each can be started in one of these ways:
- Power: the meter counts whenever the SERVER is powered. Connect the SERVER to the same power source as the equipment; no other wiring is needed. A voltage threshold stops counting as power is lost, to prevent memory corruption.
- Digital or analog input: tap a 5–24 VDC circuit on the machine and connect it to a digital input, or connect a sensor (5–24 VDC) to an input to detect the equipment’s on/off state.
- Relay: the meter counts while relay OUT1 or OUT2 is activated.
The most common setup is a sensor wired to a digital input and to the same power source as the SERVER, so the meter counts whenever the equipment is on.
Then set the trigger on the Hours page.
03Accessing the Server
Once the SERVER is powered on and connected to the network, it gets an IP address automatically via DHCP, as long as your router is set up to provide one. Enter the IP address in a web browser to open the Landing page, then click Log In at the top right.
Username admin, password admin. You can change these, or turn off the login requirement, under Settings.
Use one of the methods below to find the IP address.
Finding the IP Address with Linortek Discoverer
The Discoverer program finds the SERVER on your network automatically. It is a Java program, so Java must be installed.
- Download Linortek Discoverer from Downloads – Support Programming. Chrome or Firefox is recommended. If your browser warns about the file, choose Keep: it is a Java program and will not harm your computer.
- Run Discoverer. For each device found it shows the IP address, host name, MAC address, and other information: Blue LED (if on), product name, server software revision, and port number (if ported).
- Click the SERVER to open its web pages in your browser, then click Log In.
Internet Explorer saves Discoverer as a ZIP file by default. Choose Save as and rename the file to Linortek Discoverer.jar.
Finding the IP Address over USB
If you can’t run Discoverer, read the IP address with any terminal emulator:
- Connect the SERVER’s POWER input to a USB port on your PC.
- Find the COM port number in Windows Device Manager.
- Open a terminal emulator and connect to that COM port as a serial connection.
- Type the command below. The SERVER replies with its IP address.
Connecting Directly to a PC
With no network available, plug the SERVER directly into your PC’s Ethernet port. Unless you have set a static IP, it uses the default address 169.254.1.1. Enter it in your browser; no internet connection is needed. Once configured, install the SERVER where you need it.
04Landing and Home Pages
Landing Page
Entering the IP address (and port number, if set) opens the Landing page. It shows the SERVER name, which you can change on the Network Configuration page. The page is static, with no background activity, so it is a good place to park when you are not using the SERVER but want to keep the connection open.
Click LOGIN and enter your username and password (default admin/admin). The browser keeps your credentials until it is closed. You can turn off the login requirement on the Settings page.
Landing Page (Hour Meter Software)
With the hour meter software, the Landing page also shows the data from each hour meter:
- Up to 16 meters with independent triggers. Every meter in use is shown on the Landing page.
- Each meter records up to 999,999.99 hours, in 1/100-hour steps by default (1/10 can be selected on the Hours page).
- A running indicator spins while all conditions are met and the meter is counting.
Home Page
After you log in, the Home page shows system information and lets you locate the physical device.
| Item | Description |
|---|---|
| TIME | Current time and day of the week, in 12-hour (AM/PM) or 24-hour format. |
| DATE | Current date. |
| VOLTS | Voltage at the board. Useful for spotting voltage variation when the SERVER shares power with other equipment. |
| TEMPERATURE | Board temperature in °C or °F. It is always slightly above ambient, because of the heat the SERVER itself generates. |
| LEDs | Red: system pulse; blinks about once per second while the server runs. Green: bootloader use; generally not shown. Blue: click to turn on or off. It lights on the unit itself, so you can find it among similar units (“Locate”); Discoverer also shows when it is on. |
05Relays and Inputs
In/Out Page
The Services menu changes with the SERVER’s configuration. It is where you control inputs, outputs, sensors and other special controls. Depending on the software, its first page is In/Out (relays and inputs together) or Relays (relays only).
Select Services – In/Out. The Ultra 300 has two relays (Relay 1, Relay 2), two digital inputs (DIN1, DIN2) and two analog inputs (AN1, AN2). You can rename all of them.
Relay Control
The first section of the In/Out page lists the relays. The State LED shows whether a relay is on (green) or off (red); click it to switch the relay manually. Each relay can have a name and labels for its NO, C and NC connections. Four status LEDs show:
| LED | On when |
|---|---|
| An email is sent when the relay switches on or off. | |
| Pulse | A pulse width and multiplier (duration) are set (see Set Relay). |
| Sched. | A task on the Tasks page triggers this relay. |
| Timed | Turns red while a pulsed relay is running on its timer. |
Click the Edit icon on a relay line to open its Set Relay page.
Set Relay Page
| Field | Description |
|---|---|
| Relay Select | The relay line you clicked. |
| Name | 15 characters, letters and numbers only. This and the NO/C/NC labels can hold any identifying information. |
| Pulse Width | 0 = no timed pulse; any other number (up to 4 digits, e.g. 1234) turns the relay on for that duration. |
| Pulse Width Multiplier | Unit for the pulse width: None, mS (1/1000 s), Sec or Min. |
| Relay Type | Normal: relay on this SERVER · Latched: not currently supported · Remote: a relay on another Linortek device, over the network · Zigbee: a relay on a remote device, over RF · Normal and Remote / Normal and Zigbee: both relays · Remote BELL: a bell at a remote location (bell software only) · Normal and Remote BELL: local and remote bells (bell software only). |
| Location ID | Number of the remote location (see Remote Devices). |
| Relay at Location | Number of the relay or device at that location. |
| Send Email | Send an email when the relay turns on or off (see Email Setup). |
4 Relays (Bell Software)
The Ultra 300 has 2 physical relays. The bell software adds 2 virtual relays, so the SERVER can control extra slave controllers. Open them under Services – 4 Relays and set them up as described in Relay Control.
Inputs
The In/Out page shows a box for each input. At the top is its label, such as DIN 1 (digital) or AIN 2 (analog), which turns green when the input is enabled. Inside is the display set on the input’s settings page. A dot at the lower left shows the state of a linked relay, if any (red off, green on), and the Edit icon at the lower right opens the Set Digital Input or Set Analog Input page.
Set Digital Input Page
Digital inputs can show their data in several display types, with a name and an associated relay (green/red, and clickable to control it).
| Field | Description |
|---|---|
| Digital Input Selected | The input you are editing. |
| Name | 15 characters, letters and numbers only; shown in the bar at the top of the display. |
| Label | 7 characters; shown on the display itself. |
| Corrector | Add, subtract, multiply or divide the value before it is displayed. Up to two operations separated by a space, using +, -, * or / (e.g. *3 +2). |
| USE | Activates the input; its number turns green. Active inputs use CPU time, so turn on only the ones you need. |
| Type | State (on/off, e.g. a door switch) · CounterNR (non-resettable counter) · CounterR (resettable counter) · Frequency (e.g. a tachometer; 1 Hz = 60 RPM) · Period (in milliseconds; for timing events). |
| Display | Dot (value in a colored dot, label below; good for State) · Values (value with the label below) · Meter (dial scaled by Min/Max, with colored arcs and the label inside) · VBar (vertical bar scaled by Min/Max, colored by range). |
| Relay L/T | A relay number to show and control from this display (any relay, on any input). Add L (e.g. 2L) to make the input follow the relay, or T to make the relay follow the input. |
| Command Z/N/I | Z zero the resettable counter · N normal input · I invert the input. |
| Value Min/Max | Display range, after the Corrector. A Meter can’t go past Max, so set Max to at least 1. |
| Yellow / Red / Green | Value ranges for each color, after the Corrector. For a State input, use Red 0–0, Green 1–1 and Yellow 2–2, so yellow is never used. |
Set Analog Input Page
Analog inputs use the same Name, Label, USE, Display, Relay, Value and color fields as digital inputs (the Relay field has no L/T option). The Corrector and Type fields differ:
| Field | Description |
|---|---|
| Corrector | As for digital inputs. For a thermistor, enter its values instead: T (thermistor resistance), B (beta value), R (external resistor), V (voltage), e.g. T10000 B3892 R10000 V4.77. |
| Type | Analog 1 / Analog 2: analog inputs AN1/AN2 · AC Current 1 / AC Current 2: AC current sensor on AN1/AN2 · AC Current 3: not used · Volts: voltage powering the SERVER · Current: current drawn by the SERVER · Int. Temp: on-board temperature sensor · Ext. Temp / R. Humidity: temperature and % relative humidity from the AM2302 sensor (sold separately) · MMA X / MMA Y / MMA Z: accelerometer axes. |
06Hour Meter (Hour Meter Software)
Hours Page
After wiring the SERVER to your equipment (see Activate the Meter), turn on and configure the meters under Services – Hours. The page has one column per meter, with identical settings.
| Field | Description |
|---|---|
| Use Meter | Must be checked for the meter to run. |
| Trigger | What starts and stops counting: an INPUT, a RELAY, or the INPUT VOLTAGE (the meter runs whenever the SERVER is powered). |
| Meter Name | Identifies what is being metered. |
| Seconds/Tick | Counting resolution. Smaller numbers wear the memory faster; usually set to 2. |
| Used Endurance | The memory allows a finite number of writes and will wear out. This shows how much of it is used. Endurance in seconds = Tick × 512 × 100,000. |
| Voltage Threshold | Must be met along with the trigger for the meter to count, so it stops before a power loss can corrupt memory. Example: on a 24 V system, a 20 V threshold stops the meter as power declines. |
| Send Email / Email Count | Send an email when the meter passes this value (see Email Setup). |
| Relay Control / Relay Count | Activate a relay when the meter passes this value, e.g. to turn on a maintenance light or buzzer. |
| Preset | Set the meter to zero or any other value. |
| Push Report Interval | How often, in minutes, the hour report is sent to the Hour Collector app. Default: every minute. |
| Count Hours By | Each meter records up to 999,999.99 hours, in 1/100-hour steps by default; you can change it to 1/10. |
Email Count, Relay Count and Preset can be entered in [seconds] or (hours).
Resetting the Meter Automatically
To reset a meter at regular times, for example daily, create a task on the Tasks page with Device C set to HOURMETER, Data C set to the meter number and Action set to RESET. The example below resets meter 2 every day at 12:00 AM.
07Bells and Schedules (Bell Software)
Schedules
You can create up to 10 schedules, such as a regular schedule, teacher work days and holidays. Bell events belong to a schedule, so set up your schedules first.
- Go to Services – Schedules. A default schedule, Schedule 1, is already in use; it can’t be deleted until you add another.
- In the Add section at the bottom of the page, enter a name (15 characters max) and a description (32 characters max).
- Click Add.
Adding Bell Events
Each schedule can hold up to 500 events. Select the schedule first, then go to Services – Bells. The add section is at the bottom of the page.
| Field | Description |
|---|---|
| Name | 15 characters max, no special characters. |
| Time | 24-hour format, HH:MM:SS. |
| Date | Optional. If set, the bell rings only on this date; the days of the week are disabled and the date is shown instead. |
| Duration | A number from 1 to 99 and a unit (mS, Sec or Min). If left empty, the bell rings for 1 millisecond. |
Click Add. New events use bells 1 and 2, Monday to Friday, by default. Click a pip under a bell or day to change it: selected pips are green, others grey. Click SAVE after changing pips. Click DEL at the end of an event to delete it, or Reset to delete all events.
Downloading Bell Events
Save your events to a text file, to keep a copy or to reuse them on other schedules or devices.
- On Services – Bells, click DOWNLOAD. A new window shows your events, starting with
#Start. - Create a .txt file and paste the events into it, including
#Startat the very beginning. - Save the file.
Bell Event File Format
You can edit the events in the text file before uploading them. The file always starts with #Start, followed by one event per line, with the values separated by commas in this order:
| Value | Format |
|---|---|
| Name | Any words, 15 characters max. |
| Hour, Minute, Second | 2 digits each, 24-hour format (3 PM = 15). |
| Year, Month, Day | 2 digits each. Use 00,00,00 for an event that repeats on its days of the week. |
| Bells | 8 digits, one per bell: 1 = ring, 0 = don’t ring. The Ultra 300 uses the first 4 (2 physical and 2 virtual bells); 11110000 rings all four. |
| Day of week | 7 digits, Sunday to Saturday: 1 = ring that day. Monday to Friday = 0111110. |
| Duration | 1 to 99. |
| Duration multiplier | Ms, Sec or Min. |
| Use | 1 = in use, 0 = not in use. |
| Once | 1 = run once only, 0 = normal schedule. |
Example template: a weekday schedule ringing bell 1 for 5 seconds. Copy it, paste it into a .txt file and edit as needed.
| Name | HH,MM,SS | YY,MM,DD | Bells | Days | Duration | Use,Once |
|---|---|---|---|---|---|---|
| Morning | 07,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| 8AM | 08,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| Form | 08,30,00 | 00,00,00 | 00000000 | 0111110 | 5,Sec | 1,0 |
| 9AM | 09,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| 10AM | 10,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| 11AM | 11,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| Noon | 12,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| Lunch | 12,30,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| Back from lunch | 13,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| 2PM | 14,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| Second shift | 15,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
| End of Day | 17,00,00 | 00,00,00 | 10000000 | 0111110 | 5,Sec | 1,0 |
Uploading Bell Events
- Select the schedule that should use the events.
- On Services – Bells, click Upload.
- Browse to your .txt file and click Upload.
- Return to the Bells page. The events are listed, with the number of records uploaded.
08Tasks (Automatic Events)
Tasks Page
The Tasks page lists up to 64 automatic events. Each is an IF … THEN statement whose IF part can have two terms: IF a AND/OR/NOT b THEN c. Click the dot in the Use column to turn a task on (green) or off (red), and click the Edit icon to create or change it.
Set Task Page
| Field | Description |
|---|---|
| Task Select | The task line you clicked. |
| Task Name | 15 characters. |
| USE | Must be checked for the task to run. It unchecks itself if the data has an error. |
| LOG | Write to the system log every time the task runs. |
| Send an email every time the task runs. | |
| Device A / Data A | The first IF condition (see data formats). On an error, USE unchecks and the faulty field is highlighted when you click Save. |
| Logic | AND: A and B are both true · OR: A or B is true · NOT: A is true and B is not. |
| Device B / Data B | The second IF condition, in the same formats. |
| Device C / Data C | What to control (see Device C). |
| Action | ON · OFF · TGL (toggle) · RESET (reset counters). |
Data A and B Formats
| Device | Enter | Example |
|---|---|---|
| Minute | mm |
30 |
| Hour | hh (24-hour) |
14 |
| Day | dd |
01 |
| DayofWeek | Sunday = 1, Monday = 2 … Saturday = 7, Weekday = 8, Weekend = 9 | 8 |
| Time | hh:mm, 24-hour with leading zeros; seconds are ignored |
07:30 |
| Date | yy/mm/dd with leading zeros |
20/01/10 (January 10, 2020) |
| Relay | Relay number and + (on) or - (off) |
01+ |
| Button | + (on) or - (off) |
+ |
| Flag | Flag number, with + for on (optional) or - for off |
3+ |
| Temp | >, = or < and a value, always in °C |
>40 |
| Volts | >, = or < and a value |
<10 |
| Analog | Input number, >, = or <, and a value |
2<123 |
| Digital | Input number, type, >, = or <, and a value. Types (case-sensitive): S state · C non-resettable counter · c resettable counter · F frequency · P period (1/1000 s) |
1F>7500 |
Device C and Data C
| Device C | Data C |
|---|---|
| RELAY | Relays on this SERVER, up to four, separated by commas, e.g. 1,2. |
| FLAG | One of 8 storage flags that can be turned on or off, to build more complex tasks. |
| REMOTE | A relay on another Linortek device: remote unit number,remote relay, e.g. 3,5. Set up the remote units on the Remote Devices page. |
| COUNTER | Add a count to digital input counter 1 or 2. |
| BLUE LED | Turns on the blue LED. No data needed. |
| SEND EMAIL | Sends an email. Leave empty for the full JSON report; if Device A or B is an analog or digital input, enter Short for a short input report. Works with digital and analog inputs only. |
| NOTIFY | Writes the current data to the log. Analog inputs only. |
| DELAY | Delays turning a relay on: relay,seconds, e.g. 1,180. |
| HOURMETER | Meter number to reset (use with Action RESET), e.g. 1. |
| SEND UART | Not supported by the current software. |
| SEND MQTT | Leave empty for the full JSON report. To publish a single value under its own topic (e.g. lt1000/<MAC>/relay/1), enter relay/1 or relay/2, digital/1 or digital/2, hourmeter/1 to hourmeter/16, or analog/1 to analog/4. |
The example below is a typical task built this way.
Logs
The Logs page keeps over 10,000 entries for actions taken by the SERVER or by users. Each entry has a reference number, time and date, followed by the event. The log refreshes automatically.
- Use the checkboxes above the log to show or hide entries from each source.
- Use the date window to filter by date.
- Click DOWNLOAD below the log to save it as a TXT or CSV file.
09Settings
User and Admin Credentials Page
Under Settings you can set up to 3 users. Only User 1 is active by default.
| Field | Description |
|---|---|
| User Name / Password | Defaults: admin/admin, user2/user2 and user3/user3. Passwords are never displayed. |
| Active | Must be checked for the user to log in. User 1 can’t be deactivated. |
| Admin | Only admin users can save changes on most pages, which protects the SERVER from unauthorized changes. |
| Timeout | Not available at this time. |
Passwords are limited to 13 characters. If you set a longer password, you won’t be able to log in to that account.
Time/Date Page
| Field | Description |
|---|---|
| Time | hh:mm:ss, always standard time. |
| Date | yy/mm/dd. |
| Time Zone | Offset from UTC, e.g. -5 for EST, -8 for PST. Add :mm for part-hour zones, e.g. 5:30. |
| Use MIL Time | 24-hour format. |
| Use NTP Update | Synchronize the time with an NTP server. |
| Use Daylight Savings Time | Adjust the time automatically for daylight saving (not accurate in all time zones). |
| DST starts/ends | DST dates, if different from the default (North and South America). |
| Daily time correction | Correction to apply if the SERVER can’t reach an NTP server. |
| NTP Web Site | The NTP server used for updates. |
| NTP Interval | Minutes between updates. |
| Log NTP Event | Log every NTP update (normally not logged; useful for troubleshooting). |
Settings Page
| Setting | Description |
|---|---|
| Use System emails | Enables additional email messages. |
| Use Audio File System | Depends on the application; not needed for the hour meter software. |
| Use AM2302 | Use the AM2302 temperature/humidity sensor (sold separately). |
| Java Report | Send data to the Hour Collector app over Ethernet (hour meter software only). |
| Require Login | If unchecked, anyone can access the SERVER without credentials. |
| WiFi Report | Data transfer over Wi-Fi (for iTrixx Wi-Fi devices). |
| Active Landing page | Shows additional information on the Landing page. |
| Invert Relay Control | Swaps relay states between NO and NC without rewiring. |
| Use Serial Comm | Not supported. |
| Use Fahrenheit | Fahrenheit instead of Celsius. |
| Use RESTful Authentication | Require a username and password for RESTful access. |
| Extend Relay Range | Enables 8 relays. |
| Use Relay Radio Buttons | Turning one relay on turns all others off. |
| SSL Port No. | Not used here; set the HTTPS port on the Network Configuration page. |
| UART Usage | Depends on the application; not needed for the hour meter software. |
| Discovery Port | UDP port for Discoverer messages, 30303 by default. If you change it, change it in Discoverer too. |
| Select theme | Red, green or blue. |
| Upload / Download | Save the configuration file, or load a saved one. It covers relays, inputs, network settings and tasks. |
| Change Logo | Replace the Linortek logo with your own (.png, 60 kB max). |
10Configure
Network Configuration Page
Incorrect settings can make the SERVER lose its network connection. If that happens, you may need to restore the defaults with the buttons on the board.
| Field | Description |
|---|---|
| MAC Address | Unique address set at assembly; can’t be changed. |
| Host Name | The SERVER’s name on the network. It may appear in your router’s lease list, and is shown on the Home page and in Discoverer. |
| Port Number | Needed for internet access. Default: 80 (443 for HTTPS). |
| Enable DHCP | On by default. Uncheck to set a static IP address. |
| IP Address | Usually only the last group of numbers changes. Reserve the address on your router and make sure no other device uses it. |
| Gateway | Usually your router, the access point to your ISP. |
| Subnet Mask | Leave at 255.255.255.0. |
| Primary / Secondary DNS | DNS servers. |
HTTPS
To use HTTPS, set the port number to 443 and save. From then on, open the web pages at https://<IP address>:443. To choose which certificate is used, see HTTPS Config.
Access from outside your network
To reach the SERVER remotely, set a static IP address and port number here, then port forward that address on your router, so the router sends incoming traffic to the SERVER (see your router’s manual). For a stable internet address, see Dynamic DNS.
HTTPS Config Page
Under Configure – HTTPS Config you choose the certificate the SERVER uses for HTTPS connections (see Network Configuration to turn HTTPS on).
| Option | Description |
|---|---|
| Use built-in certificate | Default. The connection is encrypted, but browsers show a security warning because the certificate isn’t issued for your network; accept it to continue. |
| Use uploaded certificate | Uses a certificate you upload, for example one from your IT team, if your network requires it. |
To upload a certificate:
- Under Select new certificate, click Browse and choose the certificate file.
- Click Upload.
- Select Use uploaded certificate.
Dynamic DNS Page
Dynamic DNS, together with port forwarding on your router, gives global access to a SERVER behind a NAT router or firewall. Set a static IP address and port on the Network Configuration page first. The only supported service is DynDNS.
| Field | Description |
|---|---|
| Use DDNS | Enables the service. |
| DDNS Service | DynDNS. |
| User Name / Password | Your DynDNS account. |
| Host | The host name registered with DynDNS for this SERVER. |
Email Setup Page
Set up the email account the SERVER uses to send messages from relays, tasks and hour meters.
| Field | Description |
|---|---|
| SMTP Server | Your outgoing mail server. Your mail provider publishes this and the other settings. |
| Port | The SMTP server’s port. |
| Use SSL | 2048-bit SSL. Check only for port 465. |
| User Name / Password | Your email account. |
| To Address | The recipient. |
| Subject | Email subject line. |
CC and BCC are not supported yet.
MQTT Setup Page
MQTT (MQ Telemetry Transport) is a lightweight messaging protocol that lets devices share data and send commands to each other using very little bandwidth.
| Field | Description |
|---|---|
| MQTT Server | IP address of the computer running the MQTT broker, e.g. 192.168.1.10. |
| Port | The broker’s port; 1883 by default. |
| Username / Password | Optional; only needed if the broker requires a password. |
| Topic | The topic (channel) to use. Enter an existing topic name, or a new one to create it. Only devices connected to a topic see its messages. |
| Client ID | Required. The name the SERVER uses on the broker, e.g. “Device A”. It is separate from any username. |
IP Range Configuration Page
Reserved for future use: it will limit access to a range of IP addresses.
Remote Devices Page
Lets the SERVER control relays on up to 8 other Linortek devices (peer-to-peer), from a task or a relay set as Remote.
| Field | Description |
|---|---|
| Device Name | A name for your reference. |
| IP Address | The remote device’s IP address, including the port number. |
| User Name / Password | The remote device’s login (Basic Authentication). |
Incorrect settings make the SERVER lose its remote connections.
11System
Load/Reboot System Page
Under System – Load/Reboot System you can update the software or restore the factory defaults.
Reset to Factory Default
Resetting restores the default login (admin/admin), for example if you forgot the password.
With the buttons on the board
- Press RESET. The red LED blinks and the green LED is on (Bootload state).
- While in this state, press and hold RELOAD (DFLT) for about 10–15 seconds, until the red LED is steady.
- Release. The reset is complete when the red LED blinks once per second again.
See Board Layout Reference for the button locations.
From the web pages
- Open System – Load/Reboot System.
- Check Restore Default Values and click Boot Mode.
- The reset is complete when the red LED blinks once per second again.
Update Software
The SERVER leaves the factory with the latest software. When a new version is released:
- Download the .img file from the Linortek Downloads page.
- Open System – Load/Reboot System, check Update Software and click Boot Mode.
- In Discoverer, find the SERVER in Bootloader state and click its IP address. The upload page opens.
- Click Browse, select the .img file and click Upload.
- When “Done!!” appears, click Go to U300 app to return to the login page.
The software version is shown at the bottom of every page.
12Data Collection and Integration
Once wired and configured, the SERVER reports its data over your network. Any computer on the same network can collect it with the free Linortek apps, or through MQTT, the RESTful API, JSON or Microsoft Excel.
Hour Collector App (Hour Meter Software)
A free app for the iTrixx hour meters. It finds the SERVER automatically, gives quick access to it like Discoverer, and updates every two minutes by default (the interval can be changed in the app). It requires Java.
- Download Hour Collector (Downloads – Support Programming)
- Linortek HourMeter Collector App Setting Instruction (Downloads – Documentation)
DataCollector Pro App
A desktop app that listens for UDP broadcasts from Linortek hour meters and logs the data to a .csv file. It can also collect data manually: useful for port-forwarded hour meters, since it can read their XML pages over the internet. It also reads the Wi-Fi mini via REST or an MQTT broker.
- Download DataCollector App Pro (Downloads – Support Programming, Special Programs)
- Linortek Data Collector App Setting Instruction (Downloads – Documentation)
RESTful API and XML
Read data from the SERVER or control its inputs and outputs directly over HTTP.
MQTT
The SERVER publishes to the topic below, where xxxxxxxxxxxx is its MAC address in lower case. It sends a single JSON payload to the broker set on the MQTT Setup page, at QoS 0, on the interval you set. Tasks can also publish single values (see SEND MQTT).
For details, see the iTrixx WFMN MQTT – Product Documentation on the Downloads – Documentation page.
JSON
The SERVER also provides a JSON report on port 30000, over HTTP only (not HTTPS):
Still stuck? Our support team can help with setup and configuration.