User Manual

Ultra 300 Ethernet I/O Controller

Wiring, network access, web interface, hour meter and bell features, automated tasks, settings and data collection for the Ultra 300 controller in all its software versions.

Updated October 29, 2026 31 min read Download PDF
Overview

01Overview

The Ultra 300 is a compact Ethernet I/O controller with 2 relay outputs, 2 digital inputs, 2 analog inputs, a voltage output, an on-board temperature sensor and accelerometer, and a port for an optional temperature/humidity sensor. It is referred to as the SERVER throughout this manual.

The Ultra 300 ships with one of several software versions. Most of this manual applies to all of them; sections that apply to one version only are marked:

Software Extra features See
Standard I/O Relay and input control, tasks, logs, remote devices, MQTT and RESTful access. All sections except those marked below
Hour Meter (iTrixx) Up to 16 independent hour meters with their own landing page, email and relay alerts, and data collection apps. Activate the Meter, Hour Meter, Data Collection
Bell (Netbell) Bell events and schedules, plus 2 virtual relays for extra slave controllers. 4 Relays, Bells and Schedules

02Wiring the Server

Board Layout Reference

Figure 1Ultra 300 board layout
# Item Details
1 Relay outputs 2 signal relays, 1 Form C, 1 A @ 30 VDC. Relay 2 is on the left.
2 Voltage output Powers external devices such as a sensor. The voltage depends on how the SERVER is powered (see Voltage Output).
3 Digital inputs 2 inputs, 5–48 VDC (24–48 VDC requires the external resistor). Input 2 is on the left.
4 Analog inputs 2 inputs. Input 2 is on the left.
5 CAN inputs Not yet supported by the software.
6 Digital input switches One per input, IN2 on the left. Up = Pull-up (PU), down = Isolated (ISO).
7 RESET button Restarts the SERVER (see Reset to Factory Default).
8 RELOAD button Restores factory defaults when used with RESET.
9 RJ45 connector Ethernet network and PoE.
10 USB mini connector For the AM2302 temperature/humidity sensor (sold separately).
11 Power input Micro-USB, marked POWER; 5–24 VDC.
Caution

These units are ground-isolated. Connect so the power loop is connected only to the SERVER, and do not use external ground connections. Doing so may damage the SERVER or the PoE source device.

Power Connection

The power input is a micro-USB connector marked POWER on the enclosure. Power the SERVER in one of three ways:

  • Power supply: plug the 12 VDC power supply into an AC outlet and its cable into the POWER connector.
  • Computer: connect the POWER connector to a computer with a USB cable. This also lets you read the IP address over USB.
  • PoE: connect the RJ45 connector to a PoE network switch.
Warning

When using a PoE switch, do not also connect the 12 VDC power supply. It will damage the board.

LED Meaning
Green (Boot) flashing Bootload mode, right after power-on. In this mode the server software can be updated.
Red blinking once per second After about 5 seconds the green LED goes off: Server mode. The SERVER is reachable on the network over TCP/IP.

Network Connection

Plug an Ethernet cable into the RJ45 (NET) connector. The Connection LED on the connector comes on when it is connected to a switch with a 100 Mbps network; the Activity LED blinks to show network activity.

Relay Connections

The SERVER has 2 signal relays (1 Form C, 1 A @ 30 VDC) with push-in spring connectors, numbered OUT 1 and OUT 2. They are dry-contact relays designed for low-voltage control only: never apply more than 30 V to a relay, for your safety and to stay within the ratings of the board.

Each relay has three terminals: NO (Normally Open), C (Common) and NC (Normally Closed). When the relay activates, the connection moves from C–NC to C–NO.

  • To make a connection when the relay activates, wire between C and NO.
  • To break a circuit when the relay activates, wire between C and NC.
Figure 2Relay terminals

Voltage Output

The voltage output can power external devices, such as a sensor or an external relay. Its voltage depends on how the SERVER is powered, minus a small voltage drop:

SERVER powered by Voltage output
USB 5 V
PoE 12 V
External power supply Same as the supply voltage

The output is limited to 50 mA. Wire the positive side of the external device to the Voltage/+ terminal and, if needed, the negative side to GND.

Digital Input Connections

The two digital inputs, labeled IN1 and IN2, use push-in spring connectors. Each has two terminals: C (cathode, −) and A (anode, +).

Digital inputs detect the on/off state of an external sensor. The SERVER can show whether an input is on or off, count events (resettable or non-resettable counter), and calculate frequency (for example, as a tachometer) or period.

Each input has two modes, selected by its switch (see Board Layout Reference): down for ISO (isolated), up for PU (pull-up). They are set to ISO at the factory.

Mode How it works
PULL UP Connects a 1 kΩ resistor to an internal voltage, so you can use a simple switch (such as a magnetic door switch) across the two terminals. When the switch is activated, a signal is sent to the input.
ISOLATED You drive the opto-isolator directly with an external voltage through an internal 1 kΩ resistor. The voltage can be 5–24 V, supplying a minimum of 2 mA and a maximum of 30 mA. There is no other internal connection to this voltage.
Caution

If you use isolated mode, check the switch is set to ISO before applying an external voltage. Otherwise you may damage the SERVER or the PoE source device.

Figure 3Digital input wiring

Analog Input Connections

Analog inputs read values from external equipment such as temperature or pressure sensors. The two inputs, labeled AN1 and AN2, use push-in spring connectors with one terminal each and accept 0–5 V sensors. The SERVER provides ground and power connections, so no external voltage reference is needed.

  • 2-wire sensor: data wire to the analog input (and to a power source if needed), ground wire to GND.
  • 3-wire sensor: data wire to the analog input, ground wire to GND, power wire to Voltage/+.
Note

The analog inputs are not isolated. Use an isolated sensor that makes no connection to a remote ground.

Figure 4Analog input wiring

Activate the Meter (Hour Meter Software)

The hour meter software has up to 16 separate hour counters, each with its own trigger. Each can be started in one of these ways:

  1. Power: the meter counts whenever the SERVER is powered. Connect the SERVER to the same power source as the equipment; no other wiring is needed. A voltage threshold stops counting as power is lost, to prevent memory corruption.
  2. Digital or analog input: tap a 5–24 VDC circuit on the machine and connect it to a digital input, or connect a sensor (5–24 VDC) to an input to detect the equipment’s on/off state.
  3. Relay: the meter counts while relay OUT1 or OUT2 is activated.
Tip

The most common setup is a sensor wired to a digital input and to the same power source as the SERVER, so the meter counts whenever the equipment is on.

Then set the trigger on the Hours page.

03Accessing the Server

Once the SERVER is powered on and connected to the network, it gets an IP address automatically via DHCP, as long as your router is set up to provide one. Enter the IP address in a web browser to open the Landing page, then click Log In at the top right.

Default login

Username admin, password admin. You can change these, or turn off the login requirement, under Settings.

Use one of the methods below to find the IP address.

Finding the IP Address with Linortek Discoverer

The Discoverer program finds the SERVER on your network automatically. It is a Java program, so Java must be installed.

  1. Download Linortek Discoverer from Downloads – Support Programming. Chrome or Firefox is recommended. If your browser warns about the file, choose Keep: it is a Java program and will not harm your computer.
  2. Run Discoverer. For each device found it shows the IP address, host name, MAC address, and other information: Blue LED (if on), product name, server software revision, and port number (if ported).
  3. Click the SERVER to open its web pages in your browser, then click Log In.
Figure 5Linortek Discoverer
Internet Explorer

Internet Explorer saves Discoverer as a ZIP file by default. Choose Save as and rename the file to Linortek Discoverer.jar.

Finding the IP Address over USB

If you can’t run Discoverer, read the IP address with any terminal emulator:

  1. Connect the SERVER’s POWER input to a USB port on your PC.
  2. Find the COM port number in Windows Device Manager.
  3. Open a terminal emulator and connect to that COM port as a serial connection.
  4. Type the command below. The SERVER replies with its IP address.
netinfo
Figure 6netinfo output in a terminal emulator

Connecting Directly to a PC

With no network available, plug the SERVER directly into your PC’s Ethernet port. Unless you have set a static IP, it uses the default address 169.254.1.1. Enter it in your browser; no internet connection is needed. Once configured, install the SERVER where you need it.

http://169.254.1.1

04Landing and Home Pages

Landing Page

Entering the IP address (and port number, if set) opens the Landing page. It shows the SERVER name, which you can change on the Network Configuration page. The page is static, with no background activity, so it is a good place to park when you are not using the SERVER but want to keep the connection open.

Click LOGIN and enter your username and password (default admin/admin). The browser keeps your credentials until it is closed. You can turn off the login requirement on the Settings page.

Landing Page (Hour Meter Software)

With the hour meter software, the Landing page also shows the data from each hour meter:

  • Up to 16 meters with independent triggers. Every meter in use is shown on the Landing page.
  • Each meter records up to 999,999.99 hours, in 1/100-hour steps by default (1/10 can be selected on the Hours page).
  • A running indicator spins while all conditions are met and the meter is counting.
Figure 7Hour meter landing page

Home Page

After you log in, the Home page shows system information and lets you locate the physical device.

Item Description
TIME Current time and day of the week, in 12-hour (AM/PM) or 24-hour format.
DATE Current date.
VOLTS Voltage at the board. Useful for spotting voltage variation when the SERVER shares power with other equipment.
TEMPERATURE Board temperature in °C or °F. It is always slightly above ambient, because of the heat the SERVER itself generates.
LEDs Red: system pulse; blinks about once per second while the server runs. Green: bootloader use; generally not shown. Blue: click to turn on or off. It lights on the unit itself, so you can find it among similar units (“Locate”); Discoverer also shows when it is on.
Figure 8Home page

05Relays and Inputs

In/Out Page

The Services menu changes with the SERVER’s configuration. It is where you control inputs, outputs, sensors and other special controls. Depending on the software, its first page is In/Out (relays and inputs together) or Relays (relays only).

Select Services – In/Out. The Ultra 300 has two relays (Relay 1, Relay 2), two digital inputs (DIN1, DIN2) and two analog inputs (AN1, AN2). You can rename all of them.

Figure 9In/Out page

Relay Control

The first section of the In/Out page lists the relays. The State LED shows whether a relay is on (green) or off (red); click it to switch the relay manually. Each relay can have a name and labels for its NO, C and NC connections. Four status LEDs show:

LED On when
Email An email is sent when the relay switches on or off.
Pulse A pulse width and multiplier (duration) are set (see Set Relay).
Sched. A task on the Tasks page triggers this relay.
Timed Turns red while a pulsed relay is running on its timer.
Figure 10Relay Control

Click the Edit icon on a relay line to open its Set Relay page.

Set Relay Page

Field Description
Relay Select The relay line you clicked.
Name 15 characters, letters and numbers only. This and the NO/C/NC labels can hold any identifying information.
Pulse Width 0 = no timed pulse; any other number (up to 4 digits, e.g. 1234) turns the relay on for that duration.
Pulse Width Multiplier Unit for the pulse width: None, mS (1/1000 s), Sec or Min.
Relay Type Normal: relay on this SERVER · Latched: not currently supported · Remote: a relay on another Linortek device, over the network · Zigbee: a relay on a remote device, over RF · Normal and Remote / Normal and Zigbee: both relays · Remote BELL: a bell at a remote location (bell software only) · Normal and Remote BELL: local and remote bells (bell software only).
Location ID Number of the remote location (see Remote Devices).
Relay at Location Number of the relay or device at that location.
Send Email Send an email when the relay turns on or off (see Email Setup).
Figure 11Set Relay page

4 Relays (Bell Software)

The Ultra 300 has 2 physical relays. The bell software adds 2 virtual relays, so the SERVER can control extra slave controllers. Open them under Services – 4 Relays and set them up as described in Relay Control.

Inputs

The In/Out page shows a box for each input. At the top is its label, such as DIN 1 (digital) or AIN 2 (analog), which turns green when the input is enabled. Inside is the display set on the input’s settings page. A dot at the lower left shows the state of a linked relay, if any (red off, green on), and the Edit icon at the lower right opens the Set Digital Input or Set Analog Input page.

Set Digital Input Page

Digital inputs can show their data in several display types, with a name and an associated relay (green/red, and clickable to control it).

Field Description
Digital Input Selected The input you are editing.
Name 15 characters, letters and numbers only; shown in the bar at the top of the display.
Label 7 characters; shown on the display itself.
Corrector Add, subtract, multiply or divide the value before it is displayed. Up to two operations separated by a space, using +, -, * or / (e.g. *3 +2).
USE Activates the input; its number turns green. Active inputs use CPU time, so turn on only the ones you need.
Type State (on/off, e.g. a door switch) · CounterNR (non-resettable counter) · CounterR (resettable counter) · Frequency (e.g. a tachometer; 1 Hz = 60 RPM) · Period (in milliseconds; for timing events).
Display Dot (value in a colored dot, label below; good for State) · Values (value with the label below) · Meter (dial scaled by Min/Max, with colored arcs and the label inside) · VBar (vertical bar scaled by Min/Max, colored by range).
Relay L/T A relay number to show and control from this display (any relay, on any input). Add L (e.g. 2L) to make the input follow the relay, or T to make the relay follow the input.
Command Z/N/I Z zero the resettable counter · N normal input · I invert the input.
Value Min/Max Display range, after the Corrector. A Meter can’t go past Max, so set Max to at least 1.
Yellow / Red / Green Value ranges for each color, after the Corrector. For a State input, use Red 0–0, Green 1–1 and Yellow 2–2, so yellow is never used.
Figure 12Set Digital Input page

Set Analog Input Page

Analog inputs use the same Name, Label, USE, Display, Relay, Value and color fields as digital inputs (the Relay field has no L/T option). The Corrector and Type fields differ:

Field Description
Corrector As for digital inputs. For a thermistor, enter its values instead: T (thermistor resistance), B (beta value), R (external resistor), V (voltage), e.g. T10000 B3892 R10000 V4.77.
Type Analog 1 / Analog 2: analog inputs AN1/AN2 · AC Current 1 / AC Current 2: AC current sensor on AN1/AN2 · AC Current 3: not used · Volts: voltage powering the SERVER · Current: current drawn by the SERVER · Int. Temp: on-board temperature sensor · Ext. Temp / R. Humidity: temperature and % relative humidity from the AM2302 sensor (sold separately) · MMA X / MMA Y / MMA Z: accelerometer axes.
Figure 13Set Analog Input page

06Hour Meter (Hour Meter Software)

Hours Page

After wiring the SERVER to your equipment (see Activate the Meter), turn on and configure the meters under Services – Hours. The page has one column per meter, with identical settings.

Field Description
Use Meter Must be checked for the meter to run.
Trigger What starts and stops counting: an INPUT, a RELAY, or the INPUT VOLTAGE (the meter runs whenever the SERVER is powered).
Meter Name Identifies what is being metered.
Seconds/Tick Counting resolution. Smaller numbers wear the memory faster; usually set to 2.
Used Endurance The memory allows a finite number of writes and will wear out. This shows how much of it is used. Endurance in seconds = Tick × 512 × 100,000.
Voltage Threshold Must be met along with the trigger for the meter to count, so it stops before a power loss can corrupt memory. Example: on a 24 V system, a 20 V threshold stops the meter as power declines.
Send Email / Email Count Send an email when the meter passes this value (see Email Setup).
Relay Control / Relay Count Activate a relay when the meter passes this value, e.g. to turn on a maintenance light or buzzer.
Preset Set the meter to zero or any other value.
Push Report Interval How often, in minutes, the hour report is sent to the Hour Collector app. Default: every minute.
Count Hours By Each meter records up to 999,999.99 hours, in 1/100-hour steps by default; you can change it to 1/10.

Email Count, Relay Count and Preset can be entered in [seconds] or (hours).

Figure 14Hours page

Resetting the Meter Automatically

To reset a meter at regular times, for example daily, create a task on the Tasks page with Device C set to HOURMETER, Data C set to the meter number and Action set to RESET. The example below resets meter 2 every day at 12:00 AM.

Figure 15Task that resets meter 2 daily

07Bells and Schedules (Bell Software)

Schedules

You can create up to 10 schedules, such as a regular schedule, teacher work days and holidays. Bell events belong to a schedule, so set up your schedules first.

  1. Go to Services – Schedules. A default schedule, Schedule 1, is already in use; it can’t be deleted until you add another.
  2. In the Add section at the bottom of the page, enter a name (15 characters max) and a description (32 characters max).
  3. Click Add.
Figure 16Schedules page

Adding Bell Events

Each schedule can hold up to 500 events. Select the schedule first, then go to Services – Bells. The add section is at the bottom of the page.

Field Description
Name 15 characters max, no special characters.
Time 24-hour format, HH:MM:SS.
Date Optional. If set, the bell rings only on this date; the days of the week are disabled and the date is shown instead.
Duration A number from 1 to 99 and a unit (mS, Sec or Min). If left empty, the bell rings for 1 millisecond.

Click Add. New events use bells 1 and 2, Monday to Friday, by default. Click a pip under a bell or day to change it: selected pips are green, others grey. Click SAVE after changing pips. Click DEL at the end of an event to delete it, or Reset to delete all events.

Figure 17Bells page

Downloading Bell Events

Save your events to a text file, to keep a copy or to reuse them on other schedules or devices.

  1. On Services – Bells, click DOWNLOAD. A new window shows your events, starting with #Start.
  2. Create a .txt file and paste the events into it, including #Start at the very beginning.
  3. Save the file.

Bell Event File Format

You can edit the events in the text file before uploading them. The file always starts with #Start, followed by one event per line, with the values separated by commas in this order:

Value Format
Name Any words, 15 characters max.
Hour, Minute, Second 2 digits each, 24-hour format (3 PM = 15).
Year, Month, Day 2 digits each. Use 00,00,00 for an event that repeats on its days of the week.
Bells 8 digits, one per bell: 1 = ring, 0 = don’t ring. The Ultra 300 uses the first 4 (2 physical and 2 virtual bells); 11110000 rings all four.
Day of week 7 digits, Sunday to Saturday: 1 = ring that day. Monday to Friday = 0111110.
Duration 1 to 99.
Duration multiplier Ms, Sec or Min.
Use 1 = in use, 0 = not in use.
Once 1 = run once only, 0 = normal schedule.
Figure 18Bell event file

Example template: a weekday schedule ringing bell 1 for 5 seconds. Copy it, paste it into a .txt file and edit as needed.

Name HH,MM,SS YY,MM,DD Bells Days Duration Use,Once
Morning 07,00,00 00,00,00 10000000 0111110 5,Sec 1,0
8AM 08,00,00 00,00,00 10000000 0111110 5,Sec 1,0
Form 08,30,00 00,00,00 00000000 0111110 5,Sec 1,0
9AM 09,00,00 00,00,00 10000000 0111110 5,Sec 1,0
10AM 10,00,00 00,00,00 10000000 0111110 5,Sec 1,0
11AM 11,00,00 00,00,00 10000000 0111110 5,Sec 1,0
Noon 12,00,00 00,00,00 10000000 0111110 5,Sec 1,0
Lunch 12,30,00 00,00,00 10000000 0111110 5,Sec 1,0
Back from lunch 13,00,00 00,00,00 10000000 0111110 5,Sec 1,0
2PM 14,00,00 00,00,00 10000000 0111110 5,Sec 1,0
Second shift 15,00,00 00,00,00 10000000 0111110 5,Sec 1,0
End of Day 17,00,00 00,00,00 10000000 0111110 5,Sec 1,0
#Start … 12 example events

Uploading Bell Events

  1. Select the schedule that should use the events.
  2. On Services – Bells, click Upload.
  3. Browse to your .txt file and click Upload.
  4. Return to the Bells page. The events are listed, with the number of records uploaded.

08Tasks (Automatic Events)

Tasks Page

The Tasks page lists up to 64 automatic events. Each is an IF … THEN statement whose IF part can have two terms: IF a AND/OR/NOT b THEN c. Click the dot in the Use column to turn a task on (green) or off (red), and click the Edit icon to create or change it.

Figure 19Tasks page

Set Task Page

Field Description
Task Select The task line you clicked.
Task Name 15 characters.
USE Must be checked for the task to run. It unchecks itself if the data has an error.
LOG Write to the system log every time the task runs.
Email Send an email every time the task runs.
Device A / Data A The first IF condition (see data formats). On an error, USE unchecks and the faulty field is highlighted when you click Save.
Logic AND: A and B are both true · OR: A or B is true · NOT: A is true and B is not.
Device B / Data B The second IF condition, in the same formats.
Device C / Data C What to control (see Device C).
Action ON · OFF · TGL (toggle) · RESET (reset counters).

Data A and B Formats

Device Enter Example
Minute mm 30
Hour hh (24-hour) 14
Day dd 01
DayofWeek Sunday = 1, Monday = 2 … Saturday = 7, Weekday = 8, Weekend = 9 8
Time hh:mm, 24-hour with leading zeros; seconds are ignored 07:30
Date yy/mm/dd with leading zeros 20/01/10 (January 10, 2020)
Relay Relay number and + (on) or - (off) 01+
Button + (on) or - (off) +
Flag Flag number, with + for on (optional) or - for off 3+
Temp >, = or < and a value, always in °C >40
Volts >, = or < and a value <10
Analog Input number, >, = or <, and a value 2<123
Digital Input number, type, >, = or <, and a value. Types (case-sensitive): S state · C non-resettable counter · c resettable counter · F frequency · P period (1/1000 s) 1F>7500

Device C and Data C

Device C Data C
RELAY Relays on this SERVER, up to four, separated by commas, e.g. 1,2.
FLAG One of 8 storage flags that can be turned on or off, to build more complex tasks.
REMOTE A relay on another Linortek device: remote unit number,remote relay, e.g. 3,5. Set up the remote units on the Remote Devices page.
COUNTER Add a count to digital input counter 1 or 2.
BLUE LED Turns on the blue LED. No data needed.
SEND EMAIL Sends an email. Leave empty for the full JSON report; if Device A or B is an analog or digital input, enter Short for a short input report. Works with digital and analog inputs only.
NOTIFY Writes the current data to the log. Analog inputs only.
DELAY Delays turning a relay on: relay,seconds, e.g. 1,180.
HOURMETER Meter number to reset (use with Action RESET), e.g. 1.
SEND UART Not supported by the current software.
SEND MQTT Leave empty for the full JSON report. To publish a single value under its own topic (e.g. lt1000/<MAC>/relay/1), enter relay/1 or relay/2, digital/1 or digital/2, hourmeter/1 to hourmeter/16, or analog/1 to analog/4.

The example below is a typical task built this way.

Figure 20Example task

Logs

The Logs page keeps over 10,000 entries for actions taken by the SERVER or by users. Each entry has a reference number, time and date, followed by the event. The log refreshes automatically.

  • Use the checkboxes above the log to show or hide entries from each source.
  • Use the date window to filter by date.
  • Click DOWNLOAD below the log to save it as a TXT or CSV file.
Figure 21Logs page

09Settings

User and Admin Credentials Page

Under Settings you can set up to 3 users. Only User 1 is active by default.

Field Description
User Name / Password Defaults: admin/admin, user2/user2 and user3/user3. Passwords are never displayed.
Active Must be checked for the user to log in. User 1 can’t be deactivated.
Admin Only admin users can save changes on most pages, which protects the SERVER from unauthorized changes.
Timeout Not available at this time.
Important

Passwords are limited to 13 characters. If you set a longer password, you won’t be able to log in to that account.

Figure 22User and Admin Credentials page

Time/Date Page

Field Description
Time hh:mm:ss, always standard time.
Date yy/mm/dd.
Time Zone Offset from UTC, e.g. -5 for EST, -8 for PST. Add :mm for part-hour zones, e.g. 5:30.
Use MIL Time 24-hour format.
Use NTP Update Synchronize the time with an NTP server.
Use Daylight Savings Time Adjust the time automatically for daylight saving (not accurate in all time zones).
DST starts/ends DST dates, if different from the default (North and South America).
Daily time correction Correction to apply if the SERVER can’t reach an NTP server.
NTP Web Site The NTP server used for updates.
NTP Interval Minutes between updates.
Log NTP Event Log every NTP update (normally not logged; useful for troubleshooting).
Figure 23Time/Date page

Settings Page

Setting Description
Use System emails Enables additional email messages.
Use Audio File System Depends on the application; not needed for the hour meter software.
Use AM2302 Use the AM2302 temperature/humidity sensor (sold separately).
Java Report Send data to the Hour Collector app over Ethernet (hour meter software only).
Require Login If unchecked, anyone can access the SERVER without credentials.
WiFi Report Data transfer over Wi-Fi (for iTrixx Wi-Fi devices).
Active Landing page Shows additional information on the Landing page.
Invert Relay Control Swaps relay states between NO and NC without rewiring.
Use Serial Comm Not supported.
Use Fahrenheit Fahrenheit instead of Celsius.
Use RESTful Authentication Require a username and password for RESTful access.
Extend Relay Range Enables 8 relays.
Use Relay Radio Buttons Turning one relay on turns all others off.
SSL Port No. Not used here; set the HTTPS port on the Network Configuration page.
UART Usage Depends on the application; not needed for the hour meter software.
Discovery Port UDP port for Discoverer messages, 30303 by default. If you change it, change it in Discoverer too.
Select theme Red, green or blue.
Upload / Download Save the configuration file, or load a saved one. It covers relays, inputs, network settings and tasks.
Change Logo Replace the Linortek logo with your own (.png, 60 kB max).
Figure 24Settings page

10Configure

Network Configuration Page

Caution

Incorrect settings can make the SERVER lose its network connection. If that happens, you may need to restore the defaults with the buttons on the board.

Field Description
MAC Address Unique address set at assembly; can’t be changed.
Host Name The SERVER’s name on the network. It may appear in your router’s lease list, and is shown on the Home page and in Discoverer.
Port Number Needed for internet access. Default: 80 (443 for HTTPS).
Enable DHCP On by default. Uncheck to set a static IP address.
IP Address Usually only the last group of numbers changes. Reserve the address on your router and make sure no other device uses it.
Gateway Usually your router, the access point to your ISP.
Subnet Mask Leave at 255.255.255.0.
Primary / Secondary DNS DNS servers.
Figure 25Network Configuration page

HTTPS

To use HTTPS, set the port number to 443 and save. From then on, open the web pages at https://<IP address>:443. To choose which certificate is used, see HTTPS Config.

Access from outside your network

To reach the SERVER remotely, set a static IP address and port number here, then port forward that address on your router, so the router sends incoming traffic to the SERVER (see your router’s manual). For a stable internet address, see Dynamic DNS.

HTTPS Config Page

Under Configure – HTTPS Config you choose the certificate the SERVER uses for HTTPS connections (see Network Configuration to turn HTTPS on).

Option Description
Use built-in certificate Default. The connection is encrypted, but browsers show a security warning because the certificate isn’t issued for your network; accept it to continue.
Use uploaded certificate Uses a certificate you upload, for example one from your IT team, if your network requires it.

To upload a certificate:

  1. Under Select new certificate, click Browse and choose the certificate file.
  2. Click Upload.
  3. Select Use uploaded certificate.
Figure 26HTTPS Config page

Dynamic DNS Page

Dynamic DNS, together with port forwarding on your router, gives global access to a SERVER behind a NAT router or firewall. Set a static IP address and port on the Network Configuration page first. The only supported service is DynDNS.

Field Description
Use DDNS Enables the service.
DDNS Service DynDNS.
User Name / Password Your DynDNS account.
Host The host name registered with DynDNS for this SERVER.
Figure 27Dynamic DNS page

Email Setup Page

Set up the email account the SERVER uses to send messages from relays, tasks and hour meters.

Field Description
SMTP Server Your outgoing mail server. Your mail provider publishes this and the other settings.
Port The SMTP server’s port.
Use SSL 2048-bit SSL. Check only for port 465.
User Name / Password Your email account.
To Address The recipient.
Subject Email subject line.
Note

CC and BCC are not supported yet.

Figure 28Email Setup page

MQTT Setup Page

MQTT (MQ Telemetry Transport) is a lightweight messaging protocol that lets devices share data and send commands to each other using very little bandwidth.

Field Description
MQTT Server IP address of the computer running the MQTT broker, e.g. 192.168.1.10.
Port The broker’s port; 1883 by default.
Username / Password Optional; only needed if the broker requires a password.
Topic The topic (channel) to use. Enter an existing topic name, or a new one to create it. Only devices connected to a topic see its messages.
Client ID Required. The name the SERVER uses on the broker, e.g. “Device A”. It is separate from any username.
Figure 29MQTT Setup page

IP Range Configuration Page

Reserved for future use: it will limit access to a range of IP addresses.

Remote Devices Page

Lets the SERVER control relays on up to 8 other Linortek devices (peer-to-peer), from a task or a relay set as Remote.

Field Description
Device Name A name for your reference.
IP Address The remote device’s IP address, including the port number.
User Name / Password The remote device’s login (Basic Authentication).
Caution

Incorrect settings make the SERVER lose its remote connections.

Figure 30Remote Devices page

11System

Load/Reboot System Page

Under System – Load/Reboot System you can update the software or restore the factory defaults.

Figure 31Load/Reboot System page

Reset to Factory Default

Resetting restores the default login (admin/admin), for example if you forgot the password.

With the buttons on the board

  1. Press RESET. The red LED blinks and the green LED is on (Bootload state).
  2. While in this state, press and hold RELOAD (DFLT) for about 10–15 seconds, until the red LED is steady.
  3. Release. The reset is complete when the red LED blinks once per second again.

See Board Layout Reference for the button locations.

From the web pages

  1. Open System – Load/Reboot System.
  2. Check Restore Default Values and click Boot Mode.
  3. The reset is complete when the red LED blinks once per second again.

Update Software

The SERVER leaves the factory with the latest software. When a new version is released:

  1. Download the .img file from the Linortek Downloads page.
  2. Open System – Load/Reboot System, check Update Software and click Boot Mode.
  3. In Discoverer, find the SERVER in Bootloader state and click its IP address. The upload page opens.
  4. Click Browse, select the .img file and click Upload.
  5. When “Done!!” appears, click Go to U300 app to return to the login page.

The software version is shown at the bottom of every page.

12Data Collection and Integration

Once wired and configured, the SERVER reports its data over your network. Any computer on the same network can collect it with the free Linortek apps, or through MQTT, the RESTful API, JSON or Microsoft Excel.

Hour Collector App (Hour Meter Software)

A free app for the iTrixx hour meters. It finds the SERVER automatically, gives quick access to it like Discoverer, and updates every two minutes by default (the interval can be changed in the app). It requires Java.

DataCollector Pro App

A desktop app that listens for UDP broadcasts from Linortek hour meters and logs the data to a .csv file. It can also collect data manually: useful for port-forwarded hour meters, since it can read their XML pages over the internet. It also reads the Wi-Fi mini via REST or an MQTT broker.

RESTful API and XML

Read data from the SERVER or control its inputs and outputs directly over HTTP.

MQTT

The SERVER publishes to the topic below, where xxxxxxxxxxxx is its MAC address in lower case. It sends a single JSON payload to the broker set on the MQTT Setup page, at QoS 0, on the interval you set. Tasks can also publish single values (see SEND MQTT).

lt1000/xxxxxxxxxxxx/tele

For details, see the iTrixx WFMN MQTT – Product Documentation on the Downloads – Documentation page.

JSON

The SERVER also provides a JSON report on port 30000, over HTTP only (not HTTPS):

http://<IP address>:30000

Still stuck? Our support team can help with setup and configuration.