How-To Guide
Software Update Instructions
How to load new server and webpage software on FARGO and KODA based devices, iTrixx-WFMN hour meters, and Ultra 300 and eIO-RTU controllers.
01Before You Start
Find your device in the table to see which files you need and which steps to follow. Download the software from the Software Update page, and the Discover and Bootloader programs from the Support Programming page.
| Device | Files to load | Tools | Steps |
|---|---|---|---|
| FARGO and KODA based devices: FARGO G2, KODA 100/200, Netbell-2, Netbell-K (all variants), Netbell-NTG, iTrixx-NHM | Server software (.cry) and webpage software (.bin) | Discover, Bootloader | FARGO and KODA Based Devices |
| iTrixx-WFMN-Di and WFMN-ADi | Server software (.cry) only | Discover, Bootloader, Telnet | iTrixx-WFMN |
| Ultra 300 (Netbell, iTrixx and I/O versions) and eIO-RTU (EIO-CPU) | Disc image (.img) only | A web browser | Ultra 300 and eIO-RTU |
Download the software made for your device. The software type is set at the factory, so, for example, Netbell software won’t load onto an hour meter or a standard I/O controller.
Extract the ZIP file you downloaded before you start. Video: Updating Your Linortek Device’s Software
02Allow the Bootloader Through the Firewall
The Bootloader program talks to the device over UDP port 16388. Before you use it, add an inbound rule for this port in Windows Defender Firewall. You need this for FARGO and KODA based devices and the iTrixx-WFMN, not for the Ultra 300 or eIO-RTU.
Turning the firewall off doesn’t work; you need the rule. If you don’t have permission to add it, ask your IT administrator.
- Open Control Panel – System and Security – Windows Defender Firewall.
- Click Advanced settings, then Inbound Rules, then New Rule.
- Choose Port and click Next.
- Choose UDP, enter 16388 under Specific local ports and click Next.
- Choose Allow the connection and click Next.
- Keep Domain, Private and Public checked and click Next.
- Give the rule a name, for example Linortek Bootloader, and click Finish.
When you’ve finished updating, disable or delete the rule.
03FARGO and KODA Based Devices
For FARGO G2, KODA 100/200, Netbell-2, Netbell-K, Netbell-NTG and iTrixx-NHM. Update the server software first, then the webpage software.
You need: Discover, Bootloader, the .cry and .bin files for your device, and the firewall rule.
Step 1: Find the Device
Open Discover (the Windows or the Java version) and click Refresh or Discover Devices. Click your device in the list to open its web pages in your browser. The list also shows the software version in Other Info.
Step 2: Load the File in the Bootloader
- Open the Bootloader (LinorTek Ethernet Loader Utility).
- Click File in the upper-left corner and open the .cry file you downloaded.
Step 3: Put the Device in Boot Mode
- Log in to the device’s web pages.
- Open System – Load/Reboot System.
- Leave Restore Default Values unchecked and click Boot Mode.
The device stays in Boot mode for only 5 seconds, so have the Bootloader open and ready, and start Step 4 right away. If you miss it, click Boot Mode again.
Step 4: Program the Device
- Click Locate LIA (Step 1 in the picture).
- When the LIA ID appears (the last four digits of the device’s MAC address), click Capture Target (Step 2).
- Click Program (Step 3) and wait until Programming Complete appears.
- Restart the device: click Reset LIA (Step 4), or press the RESET button on the board.
Step 5: Check the Version
Check the new software version in Discover (Other Info) or on the device’s System – Load/Reboot System page.
Step 6: Update the Webpage Software
Load the .bin file in one of two ways.
With Discover
- Check Upload Webpages.
- Click your device in the list and choose the .bin file.
- Click Upload and wait for the MPFS Updated Successful message.
- Click Site main page to open the device.
From the device’s web pages
- Open System – Load Web Pages.
- Follow the instructions on the page to upload the .bin file.
04iTrixx-WFMN
For the iTrixx-WFMN-Di and WFMN-ADi. You only load the server software (.cry); there is no webpage file.
If your device has software v0.62.4 or earlier, write down all its settings and triggers first. You need to set them up again after the update.
- Add the firewall rule.
- Load the .cry file into the device with the Bootloader: follow Steps 1 to 4 for FARGO and KODA based devices.
- Open a Telnet connection to the device’s IP address and log in.
- Enter the command upgrade. If the update worked, the device shows Upgrade available. Rebooting… and restarts.
If programming didn’t finish or failed, you see an error instead. Enter reboot, then load the file with the Bootloader again.
Windows doesn’t include Telnet by default. Turn it on under Control Panel – Programs – Turn Windows features on or off – Telnet Client.
05Ultra 300 and eIO-RTU
For all Ultra 300 versions (Netbell-Ultra 300, iTrixx-Ultra 300 and the I/O controller) and the eIO-RTU (EIO-CPU). You only upload the disc image (.img) through the web pages; you don’t need the Bootloader.
If your Ultra 300 has software v0.079 or earlier, write down all its settings first. You need to set them up again after the update.
- Log in to the device’s web pages and open System – Load/Reboot System.
- Check Update Software and click Boot Mode.
- Wait for the Linortek Image Upload page to open.
- Click Browse and select the .img file.
- Click Upload and wait 30 seconds to 3 minutes while the device updates and restarts.
Check the new version on the System – Load/Reboot System page (Software Rev).
06Need Help?
If the update doesn’t work, contact Linortek tech support or call 336-485-6199. Tell us your device model, its current software version and the file you tried to load.