How-To Guide

Reset to Factory Defaults

How to restore the factory settings and the default login on FARGO, KODA, Ultra 300, Netbell-K, Netbell-NTG, iTrixx-WFMN and eIO-RTU devices, from the web pages or with the buttons on the board.

Updated October 28, 2026 4 min read Download PDF
Before You Start

01Before You Start

A factory reset restores all settings on your device (the SERVER) to the values it had when it left the factory, including the default login admin/admin. Use it, for example, if you forgot the password or the device isn’t working as expected after changing settings.

Warning

A factory reset erases all your settings, such as schedules, network settings and notifications. Write down the settings you want to keep before you start.

There are two ways to reset:

Method Use it when
From the web pages You can still log in to the device.
With the buttons on the board You forgot the password or can’t open the web pages.

Most devices use the RESET and RELOAD buttons (RELOAD is labeled DFLT on some boards). The eIO-RTU works differently; see eIO-RTU.

02Reset from the Web Pages

  1. Log in to the device’s web pages.
  2. Open System – Load/Reboot System.
  3. Check Restore Default Values.
  4. Click Boot Mode.
  5. Wait for the device to restart. The reset is complete when the red LED blinks once per second again.

Video: Reset to Factory Default from the Software

03Reset with the Buttons

First find the RESET and RELOAD buttons on your device in Find the Buttons. On most devices you need to open the enclosure. A bent paper clip helps to press small buttons.

  1. Press and release RESET. The device enters Bootload mode: the red LED blinks rapidly and the green LED is on.
  2. While the device is in Bootload mode, press and hold RELOAD (DFLT) for about 10–15 seconds, until the red LED stops blinking rapidly and stays on.
  3. Release the button. The device restores its factory settings and restarts.
  4. The reset is complete when the red LED blinks once per second again.
Tip

Bootload mode lasts only a few seconds. If the red LED goes back to its normal 1-second blink before you press RELOAD, press RESET again and start over.

04Find the Buttons

FARGO G2 (R4G2, R8G2)

The RESET (left) and RELOAD (right) buttons are between the RJ45 network connector and the 12 VDC power connector. You don’t need to open the enclosure.

Figure 1FARGO R4G2 and R8G2

Video: Reset to Factory Default: FARGO

KODA 100 and KODA 200

Open the enclosure. The two buttons are on the right side of the board: RESET is the top button and RELOAD is the bottom button.

Figure 2KODA 100 and KODA 200

Video: Reset to Factory Default: KODA

Ultra 300

Open the enclosure. RESET (7) is in the bottom-right corner of the board, directly above the USB-C power connector. RELOAD (8) is on the left edge of the board.

Figure 3Ultra 300 board: RESET is 7, RELOAD is 8

Video: Reset to Factory Default: Ultra 300

Netbell-K (all variants)

Open the enclosure. RESET is next to the RJ45 network connector. RELOAD is in the corner of the board; its position depends on the board version (see the two boards below).

Figure 4Netbell-K, two board versions

Video: Reset to Factory Default: Netbell-K

Netbell-NTG

Remove the cover with a screwdriver. The buttons are between the RJ45 network connector and the 12 VDC power connector: RESET on the left and RELOAD on the right.

Figure 5Netbell-NTG

Video: Reset to Factory Default: Netbell-NTG

iTrixx-WFMN-Di and WFMN-ADi

Remove the cover with a screwdriver. The buttons are at the top of the board: RESET on the left and DFLT (RELOAD) on the right. Press them with a bent paper clip.

Figure 6iTrixx-WFMN-Di and WFMN-ADi

Video: Reset to Factory Default: iTrixx-WFMN

05eIO-RTU

The eIO-RTU has no RELOAD button. Use the Locate switch on the EIO-CPU instead. You can also reset it from the web pages.

  1. Power cycle the EIO-CPU: disconnect its power, then reconnect it.
  2. Within the first 5 seconds, while the green Boot LED is flashing (Bootload mode), press and hold the Locate switch with a paper clip.
  3. Keep holding until the red LED is solid, then release.

See the eIO-RTU User Manual for where the Locate switch is.

06After the Reset

  • Log in with the default user name and password: admin/admin.
  • If you can’t find the device on your network, use the free Discover program to find its IP address.
  • Set up your settings again, and change the default password.
Note

Netbell IP paging devices, such as SIP speakers and the AU-711, are reset differently. See the manual for your device on the Manuals page.

Still stuck? Our support team can help with setup and configuration.