User Manual
Netbell Network Bell Controllers
Wiring, network access, time settings, bell schedules and external triggers for the Netbell-2, Netbell-8 and all Netbell-K variants.
01Overview
This manual covers the Netbell-2, Netbell-8 and all Netbell-K variants.
All of our controllers come complete with all parts and software needed for installation, operation and control of the devices attached to them. When your kit arrives, inspect the contents of the box to make sure it is complete. The contents vary depending on which Netbell kit you purchased.
02Wiring Your Netbell
Wiring differs depending on which Netbell product you are using. Find the section below for your device.
Relay Output Connection
For relay specifications, see Board Layout Reference. To wire an external bell or buzzer to your Netbell:
- Select a power source that meets the requirements of the bell or buzzer.
- Wire one side of the power source to one side of the bell. Connect the other wire from the power supply to the Netbell’s relay terminal.
- Connect the other bell wire to the Netbell’s relay terminal.
Netbell-2
The Netbell-2 has two relay outputs, each with a removable 2-position connector. They are labeled 1 and 2 on the top of the enclosure.
Do not mix voltages or voltage types (AC or DC) on circuits connected to the relay outputs. All bells/buzzers on output 1 must use the same voltage, and all bells/buzzers on output 2 must use the same voltage. Output 1 and output 2 can use different voltages. Do not exceed 8 A at 30 VDC or 8 A at 48 VAC per output.
Netbell-8
The Netbell-8 has 8 relay outputs. Each relay has three terminals: NO (Normally Open), C (Common) and NC (Normally Closed). To wire a bell or buzzer, connect your circuit to C and NO.
Do not mix voltages or voltage types (AC or DC) on circuits connected to the relay outputs. All bells/buzzers on output 1 must use the same voltage, and all bells/buzzers on output 2 must use the same voltage. Output 1 and output 2 can use different voltages. Do not exceed 3 A at 48 VDC per output.
Netbell-K, KL, KB, M2 variants, KMB and 4K
The Netbell-K series has several products that vary in configuration:
- Netbell-K, KL and KB differ by the bell or buzzer built into the enclosure. Each has one external relay output (2 relays in total).
- M2 variants have 2 external relay outputs (3 relays in total).
- Netbell-4K has no built-in bell or buzzer and has 4 relay outputs in total.
- Netbell-KMB has no external relay outputs. It uses its on-board relays to control the tone of the built-in multi-tone siren; see Netbell-KMB.
The Netbell-K, KL, KB and M2 variants use the included power supply to power the built-in bell or buzzer. To wire an external bell or buzzer, follow the steps above, connecting it to the included bell cable. Then screw the bell cable’s circular connector onto the male connector on the enclosure.
The relays on all Netbell devices are dry contact: they do not provide power to the circuit. Your bells or buzzers need their own power supply, separate from the Netbell controller’s power supply.
Limitation of Use
Unless specifically stated, this product is NOT designed to switch line voltage devices. This limitation includes all FARGO and KODA products. To control devices that operate at line voltage, you MUST install an intermediary device such as a relay. When choosing devices to control, it is best to select low-voltage devices such as a 24 VAC bell or buzzer.
When wiring a line voltage device using an intermediary device, you MUST either be a qualified electrician or use the services of one. Local codes must be followed, including but not limited to wire gauge size and suitable housing.
Linortek cannot assume any responsibility for harm to the user or third parties from improper use of our Fargo product. This liability remains with the user. Linortek cannot assume any responsibility for damage to the device from improper use of our SERVER product.
IN NO EVENT WILL LINOR TECHNOLOGY BE LIABLE, WHETHER IN CONTRACT, TORT, OR OTHERWISE, FOR ANY INCIDENTAL, SPECIAL, INDIRECT, CONSEQUENTIAL OR PUNITIVE DAMAGES, INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR ANY LOSS OF USE, LOSS OF TIME, INCONVENIENCE, COMMERCIAL LOSS, OR LOST PROFITS, SAVINGS, OR REVENUES TO THE FULL EXTENT SUCH MAY BE DISCLAIMED BY LAW.
Power Connection
Your Netbell is supplied with a suitable power supply. On Netbell-K variants, this power supply also powers the built-in bell or buzzer. All external bells and buzzers must have their own power supply.
- Netbell-2 and Netbell-8 are supplied with a 12 VDC power supply. Plug it into any 110 VAC outlet and plug the barrel end into the 12 VDC power connector (see Board Layout Reference). The Netbell-2 can also be powered via PoE.
- Netbell-K variants are supplied with a 12 VAC or 24 VAC transformer and a power cable that must be connected to it. Insert one wire into the left terminal and the other into the right terminal, then tighten the terminals. On the 24 VAC transformer, leave the middle (GND) terminal unused; the Netbell does not use it.
Ethernet Connection
Each Netbell is supplied with an Ethernet cable. The Connection LED on the board comes on if a 100 Mbps network is available; otherwise it stays off. The Activity LED blinks to show network activity. On Netbell-K variants, these LEDs are only visible with the enclosure open. See Board Layout Reference.
Digital Input Connection
The Netbell-2 and Netbell-K variants have 2 digital inputs (5–24 VDC) on the board for triggering special notifications or emergency alerts. On Netbell-K variants, digital input 1 is connected to the enclosure and digital input 2 is accessible inside the enclosure (see Board Layout Reference). A sensor such as a temperature sensor or a push switch can be connected to a digital input.
When connecting a 12–24 VDC sensor to an input, you must use an external resistor (2.2 kΩ, 0.5 W; provided on request).
The digital inputs have two modes of operation, selected by the switch on the board marked ISO (isolated) and PU (pull-up). Put the switch up for pull-up and down for isolated.
| Mode | How it works |
|---|---|
| ISOLATED | You drive the Netbell’s opto-isolator directly with an external voltage through an internal 1 kΩ resistor. The voltage can be 5–24 VDC, supplying a minimum of 2 mA and a maximum of 30 mA to the opto-isolator diode. There is no other internal connection to this voltage, so the input is isolated. |
| PULL UP | Connects a 1 kΩ resistor to an internal voltage, so you can use a simple switch (such as a magnetic door switch) across terminals 1 and 2. When the switch is activated, a signal is sent to the input. |
Wiring a push button
For distances up to 500 ft, 20 AWG shielded wire is suitable. For distances up to 5,000 ft, use 16 AWG shielded cable instead. Longer cable runs are more susceptible to signal interference.
03Netbell-KMB
The Netbell-KMB has no external relay outputs; instead it controls a multi-tone siren. The siren plays four different tones based on a combination of DIP switches on the back of the siren, and each combination changes the four-tone set.
- Choose your tone(s) from the Netbell Standard Sound List (KMB).
- Find the DIP switch combination for those tones in Netbell-KMB Tones.
- Set the DIP switches. For their location and the volume control, see Netbell-KMB Control Board.
When setting up a bell schedule, select bells as follows. You can use the same relay combinations in Tasks.
| Tone | Bells / relays to select |
|---|---|
| Grund | 1 |
| C1 | 1 and 2 |
| C2 | 1 and 3 |
| C1 + C2 | 1, 2 and 3 |
04Netbell Clock
The Netbell-KC series can output its time to the Linortek Netbell Clock. To drive the digital clock:
- Open the Settings drop-down menu and click Settings.
- At the bottom of the middle column, in the UART Usage field, enter
clock. - Click Save.
- Plug the clock into the Netbell-KC’s clock output. The clock then takes its time from the Netbell.
The Netbell clock is set to GMT-5 by default. If you are in a different time zone, plug the clock into your Netbell-K before setting the time and date as described in Setting Time and Date.
05Accessing Your Netbell
Once your Netbell is powered on and connected to the network, it obtains an IP address via DHCP automatically, as long as your router is configured to provide one. Enter that IP address in your web browser to open the Netbell’s landing page, then click Log In at the top right. The default username and password are both admin.
Finding Your IP Address with Linortek Discoverer
The Discoverer program locates your Netbell automatically. It is a Java program, so it needs the Java Runtime installed. Download Discoverer from Support Programming.
- Chrome and Firefox are recommended. Internet Explorer saves Discoverer as a .zip file by default; choose Save as and rename the file
Linortek Discoverer.jar. - Depending on your browser’s security settings, you may see a warning asking whether to keep or discard the file. Click Keep; it is a Java program and will not harm your computer.
When Discoverer finds your device, it shows:
- IP address
- Host name
- MAC address
- Other info: blue LED (if on), product name, server software revision, port number (if ported)
Click your device in Discoverer to open its web pages in your browser, then click Login on the home page. The default username/password is admin/admin. You can change these, or disable login, in the Settings menu.
Connecting Your Netbell Directly to Your PC
If no network is available, you can plug your Netbell directly into your PC’s Ethernet port. Unless you have configured a static IP, it uses the default address 169.254.1.1. Enter 169.254.1.1 in your web browser to connect; no internet connection is needed. Once configured, you can install the Netbell where you want it.
06Server Configuration
If you are configuring your Netbell for the first time, or keeping it disconnected from the internet, use this section to set your time zone or adjust the built-in clock. Otherwise, skip ahead to Creating a Bell Schedule.
Setting Time and Date
When you first configure your Netbell, check the time and date on the home page. The Netbell is set by default to Eastern Standard Time (GMT-5) with Daylight Saving Time correction. If you are not in the Eastern time zone, set your time zone first.
An incorrect time zone may cause bells to ring at the wrong time.
- Open Settings › Time/Date from the drop-down menu.
- Enter your local time zone offset, for example
-5Eastern,-6Central,-7Mountain,-8Pacific. - Make sure Use NTP Update is checked. The Netbell then updates its time from the NTP server every 30 minutes by default.
- Click SAVE. The time updates at the next interval (30 minutes).
For an immediate update, set the standard time manually in the Time box. If you use Daylight Saving Time, enter a time one hour behind your current time; for example, at 9:35 AM, enter 8:35 AM.
To use your own internal NTP server, follow How to Use Your Internal NTP Server for Linortek Devices (PDF).
Incorrect NTP settings can stop your devices from updating their time.
If you intend to keep your Netbell off the network after configuring it, uncheck Use Daylight Savings Time and Use NTP Update. You then need to adjust the time manually for daylight saving and periodically to correct clock drift.
User and Admin Credentials
Open this page from the Settings drop-down menu. You can set up to 3 users; by default only User 1 is active.
| Setting | Description |
|---|---|
| User Name and Password | Each user has their own credentials. Defaults are admin/admin, user2/user2 and user3/user3 for Users 1, 2 and 3. Passwords are never displayed. A new password must be fewer than 13 characters. |
| Active | Must be checked for this user to sign in. User 1 cannot be deactivated. |
| Admin | Only admins can save data on most pages, which protects your Netbell from unauthorized changes. |
| Timeout | Not enabled at this time. |
07Creating a Bell Schedule
Once the time and other settings are configured, you can create your bell schedule on the Netbell’s Bells page.
Creating a Schedule on the Bells Page
Each Netbell can hold up to 500 bell events. Open the Services drop-down menu and select Bells.
An event is created in 9 steps:
- Enter an event Name of up to 15 characters, using letters and numbers only.
- Use the three Time fields to enter the time as HH:MM:SS. The hour field uses 24-hour format: select
00for 12 AM and13for 1 PM. - Optional: enter a Date. The event then triggers only on that date.
- Enter a Duration. In the second box choose mS, Sec or Min (milliseconds, seconds or minutes), then enter the amount in the first box.
- Click Add. The event appears in the list above; events are listed in chronological order.
- Choose which relay outputs the event triggers with pips 1–8 in the Bell column. 1 and 2 are selected by default. Note which numbers you use, as you will assign a sound to each.
- Choose the days of the week in the Day column (Sunday – Saturday). A specific date overrides the Day column.
- Check Use to enable the event. To trigger it only once, also check Once.
- Click Save.
Deleting Items
To delete one event, click DEL to the right of it. To clear the entire schedule, enter #!reset@memory! in the Name field and click Add.
This removes every event in the schedule. Save a copy first.
Uploading a Premade Schedule
- Enter
#uploadin the Name field and click Add. A new page opens. - Click Choose File and select your schedule in
.txtor.csvformat. - Click Upload. You return to the Bells page with your new schedule listed.
You can write a schedule in a plain text editor such as Notepad. The first line must be #Start; each following line is one event with 13 comma-separated items. Save the file as plain text (.txt). A sample schedule:
Saving Your Bell Schedule
Click Download at the bottom right of the Bells page. A new browser tab opens showing the schedule as plain text. Copy it into a plain text editor such as Notepad and save it.
Bell Scheduler Desktop App
A free desktop app for creating bell schedules is available from Support Programming. Its documentation is on the Documentation page.
08Using an External Trigger
You can program your Netbell to ring a bell from an external trigger such as a push button or a door contact switch.
Unless your trigger device supplies its own power, set the input switch to Pull Up. See Digital Input Connection and Board Layout Reference. The steps below assume digital input 1 and a bell on relay 1.
Setting the Digital Input
Open the Services drop-down menu and select Inputs or IN/OUT. The digital inputs are listed as DIN 1 and DIN 2. Click the blue pencil icon under DIN 1 and enter:
- Name – optional.
- Label – optional.
- Check Use.
- Set Type to
State. - Set Command L/Z/N/I to
i. - Click SAVE.
Setting Tasks for the Digital Input
With the trigger wired and the input configured, set up two tasks: one turns the bell on, the other turns it off.
Task 1 – bell on
- Open the Tasks page and click the Edit icon on the first available task.
- Name the task if you like, and check Use.
- Set Device A to
Digitaland Data A to1S=1. Here1is the input number,Smeans the input state, and the final1means the state is on. - Set Device C to
Relayand Data C to1. - Set Action to
ONand click Save.
Task 2 – bell off
- Click the Edit icon on a second available task.
- Enter the same settings as Task 1, but set Data A to
1S=0and Action toOFF. - Click Save.
- Door contact switch: to ring the bell when the contact is broken, swap the values:
1S=0in Task 1 and1S=1in Task 2. - Several relays: list them in Data C separated by commas, for example
1,2,3.
Ring for as long as the input is active
To keep the bell ringing while the button is pressed or the contact is broken, turn off the relay timer: open Services › Relays (or IN/OUT), click the Edit icon in the Relay Control section, clear Pulse Width, and set Pulse Width Multiplier to None. Scheduled bells override this setting.
09Netbell-KMB Tones
DIP switch combinations for the Netbell-KMB siren. Choose your tones from the Netbell Standard Sound List, then set the switches as shown. Click a table to enlarge it.
10Board Layout Reference
Although some relays are rated for higher voltages, Netbell products are not designed for use at line voltage. Do not use voltages above 48 V through the product. It is not safe. See Limitation of Use.
Netbell-2
- Digital inputs (#1 on the left), 5–24 VDC. A 12–24 VDC sensor needs an external resistor (2.2 kΩ, 0.5 W; provided on request).
- Relay outputs (#1 on the right): dry contact, 8 A @ 30 VDC, 8 A @ 48 VAC max.
- Digital input switches (IN 1 on the left)
- Reset button
- Reload button (turns on the blue LED, which identifies the unit in Discoverer)
- RJ45 connector
- Power connector (12 VDC)
- USB mini connector for the temperature/humidity sensor (sold separately)
A 12 VDC power supply is provided with the Netbell-2. It can also be powered over Ethernet (PoE).
Netbell-8
- Relay outputs (relays 1–4 on the right, top to bottom; 5–8 on the left, bottom to top): 12 VDC 5 A, 24 VDC 3 A, 48 VDC max. Each relay has NO (Normally Open), C (Common) and NC (Normally Closed) terminals.
- RJ45 connector
- Power connector (12 VDC)
- Reset button
- Reload button (turns on the blue LED, which identifies the unit in Discoverer)
A 12 VDC power supply is provided with the Netbell-8.
Netbell-K and Variants
- Relay outputs (pre-wired to the enclosure): 8 A @ 30 VDC, 8 A @ 48 VAC max.
- RJ45 connector
- Power connector (12–24 VAC)
- Digital inputs, 5–48 VDC. 12–48 VDC requires the external resistor.
- Digital input switches (IN 1 in the up position = PU mode)
- Reload button (turns on the blue LED, which identifies the unit in Discoverer)
- Reset button
- Relay outputs (relay #2 left, #3 right)
- Power connector (12–24 VAC)
- Digital input connector
- RJ45 connector
- Netbell-K, KL and KB have 2 relay outputs: relay #1 is pre-wired to the built-in bell/buzzer and the other to the enclosure.
- M2 variants have a third relay, and digital input #1 is pre-wired to the enclosure.
- Netbell-4K has 4 relays pre-wired to the enclosure.
- Netbell-K-C units and all their variants have an extra connector for the digital clock.
- Netbell-KMB and its variants have no external relay connectors.
On all models the power connector is pre-wired to the enclosure. The Netbell-K and its variants ship with the appropriate AC transformer; see Power Connection for wiring it.
Netbell-KMB Control Board
- Tone setup DIP switches
- Volume control
Factory Reset
- Press the Reset button.
- When the green LED turns on, press and hold the Reload button.
- Keep holding until the flashing red LED turns off and then turns on solid.