How-To Guide
Emergency Alarm Switches with Netbell-NTG and KODA 100
Let alarm push buttons anywhere on your network play an emergency message over the Netbell-NTG PA system, with KODA 100 controllers as remote masters and no new wiring between buildings.
01How It Works
Linortek controllers can switch each other over the network. One controller, the master, sends a signal to another, the slave. In this guide:
- The Netbell-NTG PA system is the slave, named SLAVE. It plays a pre-recorded emergency message over the speakers.
- Each alarm push button is wired to a KODA 100, the master, named Master 1 and Master 2.
When anyone presses an alarm button, its KODA 100 tells the Netbell-NTG to play the message on all speakers. The message plays once and stops; press a button again to repeat it.
This is useful for schools and factories that need alarms in several areas or buildings where running new wires is too expensive or impractical.
02What You Need
| Item | Quantity | Role |
|---|---|---|
| Netbell-NTG PA system: Netbell-NTG controller, mixer-amplifier and horn speakers | 1 system | Slave: plays the message |
| KODA 100 Ethernet I/O controller | 1 per alarm button | Master: sends the signal |
| Alarm push button | 1 per KODA 100 | Starts the alarm |
All the controllers must be on the same network (subnet).
03Wiring
Wire the Netbell-NTG PA System
Wire the Netbell-NTG, amplifier and speakers as described in Wiring the Netbell-NTG in the Netbell-NTG User Manual.
Wire the Alarm Button to the KODA 100
The KODA 100 has two digital inputs, IN1 and IN2. Connect the alarm button to either one. This guide uses IN1.
- Connect the button’s two wires to the P and C terminals of IN1.
- Open the KODA 100 enclosure and find the input switches marked IN1 and IN2.
- Set the switch for your input to DOWN. This is PU (pull-up) mode, which a plain push button needs. The factory setting is up, ISO (isolated).
For cable types and lengths, see Digital Input Connections in the KODA and FARGO User Manual.
04Network Setup
When the controllers are powered on and connected, each gets an IP address automatically (DHCP). To find them, see Finding the IP Address in the Netbell-NTG User Manual.
Then, on each controller, open Configure › Network Config and:
- Name it. Every device is called SERVER by default. Enter a clear Host Name, for example SLAVE, Master1 and Master2.
- Give it a fixed IP address. Uncheck Enable DHCP and enter the IP Address, Gateway, Subnet Mask (usually
255.255.255.0) and DNS servers. The masters find the slave by its IP address, so it must not change, for example after a power cut.
Click Save. Write down each controller’s IP address.
Wrong network settings can make a controller unreachable. Use an IP address that no other device uses, and reserve it on your router. If you lose access, see Reset to Factory Defaults.
05Set Up the Slave (Netbell-NTG)
Log in to the Netbell-NTG. This guide uses a custom message named WARNINGE.
The message must be an .ogg file with an 8-character name. A message of at least 15 seconds works best. To make one, see Creating Custom Sounds in the Netbell-NTG User Manual.
Turn On the Audio File System
Skip this if it’s already on.
- Open the SETTINGS menu and click SETTINGS.
- In UART Usage, enter
audio. - Check Use Audio File System and click SAVE.
Link the Message to a Relay
On the Netbell-NTG, a relay is only used to start a sound; nothing needs to be wired to it. You can use any relay from 1 to 8. This guide uses relay 1.
- Open the Tasks page and click the Edit icon on the first free line.
- Enter a Schedule Name if you like, for example emergency 1, and check Use.
- Set Device A to
RELAYand Data A to01+(relay 1; for relay 2 use02+, and so on). - Set Device C to
SEND UARTand Data C toPWARNINGEOGG:P, the 8-character file name, thenOGG, all in capitals. - Set Action to
ONand click SAVE.
06Set Up the Master (KODA 100)
Log in to Master 1 and make these three settings.
1. Add the Slave as a Remote Device
- Open Configure › Remote Device Config.
- On the first line, enter the Netbell-NTG’s Device Name (SLAVE), IP Address, and its login User Name and Password.
- Click Save Config.
The number at the start of the line is the slave’s Location ID. Here SLAVE is on line 1, so its ID is 1.
2. Make the Button Switch Relay 1
- Open Services › In/Out and click the Edit icon of Input 1 (the input the button is wired to).
- Fill in the Set Digital Input page as in the table below and click SAVE.
| Field | Enter |
|---|---|
| Name | Up to 15 characters, for example Alarm switch |
| USE | Checked (the input number turns green) |
| Type | State |
| Display | Any; Dot works well |
| Relay L/T | 1T: relay 1 follows the input, so pressing the button turns relay 1 on |
3. Link Relay 1 to the Slave
- On Services › In/Out, click the Edit icon of Relay 1.
- Fill in the Set Relay page as in the table below and click Save.
| Field | Enter |
|---|---|
| Name | Optional |
| Pulse Width and Multiplier | Leave at the default |
| Relay Type | Normal and Remote |
| Location ID | The slave’s line number on the Remote Device page: 1 |
| Relay at Location | The Netbell-NTG relay you linked the message to: 1 |
Now pressing the button on Master 1 turns on relay 1 on the KODA 100 and relay 1 on the Netbell-NTG, which plays the emergency message.
Master 2 and More Buttons
Set up Master 2, and any other KODA 100 with an alarm button, exactly the same way as Master 1.
07Test the System
- Press the alarm button on Master 1. The emergency message should play on all speakers, then stop.
- Repeat for Master 2 and every other button.
- Nothing plays: check that Input 1 turns green on the KODA 100’s In/Out page when you press the button. If it doesn’t, check the wiring and that the input switch is set to PU (down).
- The input works but nothing plays: check the slave’s IP address, user name and password on the Remote Device page, and the Location ID and Relay at Location on the Set Relay page.
- The relay on the Netbell-NTG turns on but nothing plays: check the Data C name on the Netbell-NTG task, and that the file is on the SD card.
Still stuck? Contact Linortek tech support or call 336-485-6199.