User Manual

iTrixx NHM Network Hour Meter

Wire, power and configure the iTrixx Network Hour Meter, and collect run-time data from its two independent hour counters.

Updated July 24, 2025 13 min read Download PDF
Overview

01Overview

Figure 1iTrixx NHM

The iTrixx Network Hour Meter (NHM) has two separate hour counters. Each can be started and stopped in one of three ways:

Trigger How it works
Power The simplest setup: the NHM counts whenever it is powered. Connect it to the same power source as the equipment you want to monitor; no other wiring is needed. A voltage threshold stops counting as power is lost, to prevent memory corruption.
Digital input One of the two digital inputs turns counting on and off, by detecting the on/off state of a sensor or circuit.
Relay The meter counts while one of the two relays is activated.

The most common setup is a digital input wired to a circuit that switches with your equipment, so the meter counts whenever the equipment is on.

02Wiring the NHM

Digital Inputs

The NHM has 2 digital inputs (5–24 VDC). They detect the on/off state of a sensor, so the NHM can show whether an input is on or off, count events (resettable or non-resettable counter), and calculate frequency (for example, as a tachometer) or period. See Board Layout Reference for their location.

Each input has two modes, selected by its switch. They are set to ISO at the factory.

Mode How it works Default state
ISOLATED (ISO) You drive the opto-isolator directly with an external voltage through an internal 1 kΩ resistor. The voltage can be 5–24 VDC, supplying a minimum of 2 mA and a maximum of 30 mA. There is no other internal connection to this voltage. ON
PULL-UP (PU) Connects a 1 kΩ resistor to an internal voltage, so you can use a simple switch (such as a magnetic door switch) across terminals 1 and 2. When the switch is activated, a signal is sent to the input. Move the switch down for this mode. OFF
Warning

If you use isolated mode, check the input switch is set to ISO before applying an external voltage. Doing otherwise may damage the NHM or the PoE source device.

Wiring Your Equipment to a Digital Input

  1. Find a 5–24 VDC circuit on your equipment that switches on and off with it.
  2. Wire this circuit to Input 1 on the NHM. For a circuit above 12 VDC, put a 2.2 kΩ resistor in line between the circuit and the NHM.
  3. Once wired, power on your equipment, then set up the input and meter as described in Configuring the Hour Meter.

The NHM only detects the voltage on this circuit; it draws no power from it and doesn’t interfere with it.

Important

Do not exceed 24 VDC on a digital input.

Figure 2Wiring the resistor to the digital input
Figure 3iTrixx NHM wiring
Figure 412–24 VDC circuit with a 2.2 kΩ inline resistor

Relay Outputs

The NHM has 2 normally-open, dry-contact relays (1 Form A, 8 A @ 48 VAC max), each on a removable 2-position connector numbered 1 and 2. Use them to control external devices or to trigger the meter. Wire devices as shown in Figure 3.

03Power and Network

Powering the NHM

Power the NHM in one of three ways:

  • The included 12 VDC power supply.
  • A 12–48 VDC circuit on your equipment: cut the barrel connector off the power supply with at least 1 in of wire, strip the ends, and tap them into the circuit. Then plug the barrel connector into the NHM. Do not exceed 48 VDC.
  • PoE.

See Board Layout Reference for the connections.

Warning

If you power the NHM from your equipment, the power circuit must be different from the circuit that triggers the hour meter. Otherwise the NHM will crash.

When using a PoE switch, do not also connect the 12 VDC power supply. It will damage the board.

Connecting to the Network

For initial configuration, connect the NHM to your network by Ethernet (or directly to your computer if no network is available). It obtains an IP address via DHCP automatically, as long as your router is configured to provide one. Enter that address in your browser, then click Log In at the top right. The default username and password are both admin.

Finding the IP Address with Discoverer

Discoverer finds your NHM automatically. It is a Java program, so it needs the Java Runtime. Download it from Support Programming.

  • Chrome and Firefox are recommended. Internet Explorer saves Discoverer as a .zip file by default; choose Save as and rename the file Linortek Discoverer.jar.
  • Depending on your browser’s security settings, you may be asked whether to keep or discard the file. Click Keep; it will not harm your computer.

Discoverer shows each device’s IP address, host name, MAC address, and other info: blue LED (if on), product name, server software revision and port number (if ported).

Figure 5Linortek Discoverer

Click your NHM in Discoverer to open its web pages, then click Login. The default username/password is admin/admin. You can change these, or turn off the login requirement, in the Settings menu.

Connecting Directly to Your PC

If no network is available, plug the NHM into your PC’s Ethernet port. Unless you have set a static IP, it uses the default address 169.254.1.1. Enter that in your browser; no internet connection is needed. Once configured, install the NHM where you want it.

04Server Configuration

If you are configuring the NHM for the first time, or keeping it off the internet, set the time zone and clock here. Otherwise skip to Configuring the Hour Meter.

NHM Landing Page

Unlike most Linortek devices, the NHM’s landing page also shows the data from both meters:

  • Two meters, each with its own trigger.
  • Each meter records up to 999,999.99 hours, in hundredths of an hour.
  • A running indicator spins while all conditions are met and the meter is counting.
Figure 6NHM landing page

Setting Time and Date

Check the time and date on the home page. The NHM is set by default to Eastern Standard Time (GMT-5) with Daylight Saving Time correction. To change this, open Settings › Time/Date and change the third box, Time Zone.

If the NHM will stay off the network, uncheck Use Daylight Savings Time and Use NTP Update. You then need to adjust the time manually for daylight saving and periodically to correct clock drift.

Figure 7Settings › Time/Date

Setting Up the Data Report

For the NHM to send data to the Hour Collector app, open Settings › Settings and make sure Java Report is enabled. WiFi Report is not used on the NHM.

Figure 8Java Report setting

05Configuring the Hour Meter

Setting the Digital Input

If a digital input triggers the meter, set it up first: open Services › In/Out and, under Inputs, click the pencil icon under DIN 1 or DIN 2. On the Set Digital Input page:

  1. Enter a Name or Label if you like.
  2. Check USE to turn the input on.
  3. Set Type to State (an on/off reading).
  4. For testing: set Display to Values. The In/Out page then shows 0 or 1, so you can check the NHM detects the circuit.
  5. To count while the circuit is off instead, enter i in Command Z/N/I.
  6. Click SAVE.

No other settings are needed to trigger the meter. For the rest, see Set Digital Input Page in the KODA/FARGO User Manual.

Figure 9Set Digital Input

The Hours Page

Open Services › Hours. There are two identical columns, one for each meter:

Setting Description
Use Meter The meter only counts when this is checked.
Trigger What starts and stops the meter: an INPUT, a RELAY, or INPUT VOLTAGE (counts whenever the NHM is powered).
Meter Name What is being metered.
Seconds/Tick Counting resolution. Smaller values use up memory faster; usually set to 2.
Used Endurance Memory can only be written a limited number of times and will wear out; this shows its condition. Endurance in seconds = Tick × 512 × 100,000.
Voltage Threshold Must be met as well as the trigger. Stops counting if power starts to drop; e.g. a threshold of 20 V on a 24 V system stops the meter before a memory error.
Send Email / Email Count Send an email when the meter passes this value, in [seconds] or (hours). The NHM is not compatible with SSL/TLS email; see Appendix.
Relay Control / Relay Count Turn on a relay when the meter passes this value, in [seconds] or (hours). Useful for a maintenance light or buzzer.
Preset Set the meter to zero or any value, in [seconds] or (hours).
Push Report Interval How often, in minutes, the hour report is sent to the Hour Collector app. Default 1 minute.
Figure 10Services › Hours

Resetting the Meter Automatically

To reset a meter on a schedule, for example daily, create a task on the Tasks page. This example resets meter 2 every day at 12:00 AM. For how tasks work, see Tasks in the KODA/FARGO User Manual.

Figure 11Task to reset meter 2 daily

06Data Collection

Once wired and configured, the NHM reports its data over your network. Any computer on the same network can collect it with the free Hour Collector or DataCollector Pro apps, the RESTful API, Microsoft Excel, or other software.

Hour Collector App

Hour Collector was made for the NHM. Download it free from Support Programming; it needs Java. It finds your NHM automatically, gives quick access like Discoverer, and updates every two minutes.

On first launch it creates a CSV_FILE folder on your desktop with a .csv log you can open in Excel. The log only updates while Hour Collector is running and the .csv file is closed.

Hour Collector shows: IP address, meter name, date/time, meter 1 and meter 2, inputs, relays, sensors, port number (if ported) and MAC address. Click DATA SELECTION to choose what is displayed. Write All Data writes everything to the .csv file whether displayed or not; uncheck it to write only the selected data.

Figure 12Hour Collector

DataCollector Pro App

DataCollector Pro is an upgraded Hour Collector. It listens for UDP broadcasts from Linortek hour meters, logs the data to .csv, shows hour readings and digital/analog input data for each meter, and can collect and export data manually or automatically. Download it from Support Programming.

Its manual mode is useful for port-forwarded hour meters: it reads data from the device’s XML pages over the internet. It can also collect data from the iTrixx Wi-Fi Hour Meter via REST or an MQTT broker.

Figure 13DataCollector Pro

Installing DataCollector Pro

  1. Run ndp48-web.exe (installs .NET Framework if needed).
  2. Run SQLServer2016-SSEI-Expr.exe. Choose a custom install and, in the feature checklist, check LocalDB at the bottom. Leave all other options at their defaults.
  3. Copy the linortek_db folder to your C: drive.
  4. Run LinorTekSetup.msi to install the app.
Note

If an older version is installed, uninstall “Linortek Data Collector App” from Control Panel › Add/Remove Programs before installing the new version.

Using DataCollector Pro

  1. Open App Settings: set the date and time format, choose automatic (listen for UDP messages; easy) or manual collection (advanced), whether to log data, and the update frequency (manual mode only).
  2. Automatic mode: open the Data Display window; data appears as it arrives.
  3. Manual mode: open the Device List and click Add Device. Enter the device type, name, IP address (local) or web address (remote), port (if assigned), and username and password. Repeat for each device, then open Data Display.
  4. In either mode, export the current data or the data log to .csv.
Important

Export the log regularly. If it grows too large, exporting can make the app stop responding; if that happens, delete the device data log.

RESTful API

These commands read data directly from the device (software revision 427 and above):

Data Address
Meter 1 count <your IP address>/api/hourmeter/1/getcount
Meter 2 count <your IP address>/api/hourmeter/2/getcount
Hours (XML) <your IP address>/hours.xml
Hour detail (XML) <your IP address>/hourdetail.xml

Microsoft Excel

You can pull hour meter data straight into Excel; see Importing data from the hour meter to a spreadsheet.

07Board Layout Reference

Board

Figure 14NHM board
  1. Digital inputs (#1 on the left), 5–48 VDC. 12–48 VDC requires the external resistor provided.
  2. Relay outputs (#1 on the right), 8 A @ 48 VAC max
  3. Digital input switches (IN 1 on the left)
  4. Reset button
  5. Reload button (turns on the blue LED, which identifies the unit in Discoverer)
  6. RJ45 connector
  7. Power connector (12 VDC)
  8. USB mini connector for the temperature/humidity sensor (sold separately)

A 12 VDC power supply is included, and the NHM can also be powered over Ethernet (PoE).

Enclosure

Figure 15NHM enclosure label
  1. Digital inputs (#1 on the left)
  2. Relay outputs (#1 on the right)
  3. Status LEDs
  4. Network connector
  5. Power input

Factory Reset

Using the buttons

  1. Press the RESET button. The red LED blinks and the green LED is on (Bootload state).
  2. While in this state, press and hold the RELOAD button for about 10–15 seconds, until the red LED comes on steady (blinking at a 1-second rate).

Using the web interface

  1. Open System › Load/Reboot System.
  2. Check Restore Default Values and click Boot Mode.
  3. The device is reset once the red LED returns to normal (blinking at a 1-second rate).

AAppendix: Sending Email Through SMTP2GO

The NHM only works with non-SSL SMTP servers, but most email providers now require SSL. A third-party SMTP delivery service that doesn’t require SSL solves this. This example uses SMTP2GO, which is free for up to 1,000 emails a month.

Step 1: Create an SMTP2GO Account

Click Sign up, choose 1K Emails on the scale and the Free plan (or a larger plan if you need more). You need a corporate email address; free services such as Gmail or Yahoo are not accepted.

Figure 16SMTP2GO sign-up

Step 2: Add an SMTP User

Log in to SMTP2GO, open Settings › SMTP Users, click Add SMTP user and fill in the form. This user is the outgoing mail account your device sends from. If you use a free address such as Yahoo or Gmail here, make sure your company mail server won’t block the messages.

Figure 17Adding an SMTP user
Figure 18SMTP2GO connection details

Step 3: Configure the NHM

On the NHM, open Configure › Email Setup:

Setting Value in this example
SMTP Server mail.smtp2go.com
Port 2525
Use SSL Unchecked
User Name / Password The SMTP2GO user from step 2
To Address Up to 3: To, CC and BCC
Subject Your subject line
Figure 19Email Setup for SMTP2GO

Click Save/Test; the NHM sends a test email straight away. If it’s not in your inbox, check the Junk or Other folder.

Step 4: Set Up Automatic Email Reports

For condition-based reports, create a task on the Tasks page; see Set Schedule Page in the KODA/FARGO User Manual. This example emails a report every day at 11:52 AM:

Figure 20Daily email task

When all the task’s conditions are met, you receive an email like this:

Figure 21Example report email

Still stuck? Our support team can help with setup and configuration.