Installation and Operation Manual

iTrixx-LHM LoRa Hour Meter System

Install, configure and operate the iTrixx-LHM LoRa server and up to 100 wireless client devices for long-range monitoring.

Updated November 6, 2026 11 min read Download PDF
Overview

01Overview

The iTrixx-LHM is a long-range wireless monitoring and control system for industrial, commercial and infrastructure sites. It has one central server and up to 100 remote client devices, which communicate over LoRa radio, so you can collect data and control equipment over long distances where wired or Wi-Fi connections are impractical.

Key Capabilities

  • Monitor remote equipment status and meter readings
  • Collect digital input signals (alarms, switches, sensors)
  • Configure automated triggers and presets
  • Store and export operational data
  • Integrate with external systems via database or JSON API

All management is done through a secure web interface.

Communication Range

LoRa (Long Range) radio is optimized for low-power, long-distance communication. The iTrixx-LHM uses the 915 MHz ISM band, license-free throughout North America. Range depends on the environment, from several hundred meters in dense industrial sites to several miles in open areas.

Best performance Reduced performance
Clear line of sight between devices Thick walls
No metal, concrete or earth in the way Steel structures
Antennas mounted high Below-grade placement
Outdoor or open areas Heavy machinery interference

System Architecture

  • One server is the main controller and data hub.
  • Multiple clients communicate wirelessly with the server.
  • All data is stored on the server, with optional export to a database.
  • You use the system through a web browser.

This gives centralized management, less wiring, and a system that is easy to scale and expand.

02System Components

Component Description
Server (iTrixx-LHM-S) Communications gateway and management server, with web configuration interface and PoE-powered Ethernet.
Client (iTrixx-LHM-C) Radio module with digital inputs and meter interfaces in an indoor/outdoor enclosure. C-AC: 100–240 VAC, 50/60 Hz. C-DC: 12–24 VDC, typically 10 mA at 12 V.

What’s in the Box

Server: LHM-S Client: LHM-C-AC Client: LHM-C-DC
Server Client Client
915 MHz antenna 915 MHz antenna 915 MHz antenna
RJ45 cable Power cable 12 VDC power supply
Digital input connector cable (2) WAGO connector (2)

03Specifications

Specification Server (LHM-S) Client (LHM-C)
Wireless technology LoRa
Frequency 915 MHz ISM band (license-free in North America)
Devices Up to 100 clients (addresses 00–99) Address set with rotary switches (00–99)
Range Up to 3 km urban / 5+ km rural (line of sight); indoors 500 m to 1+ km depending on structure
Encryption AES-128
Antenna Replaceable 915 MHz antenna
Power PoE+ (IEEE 802.3at) via Ethernet AC: 110–120 VAC plug-in or 100–240 VAC hardwired, 50/60 Hz
DC: 12–24 VDC from the supplied power adapter or the equipment’s own DC circuit, typically 10 mA at 12 V
Network 10/100/1000 Base-T Ethernet; DHCP or static IP; hostname linortek-lhm –
Web interface HTTPS web server (port 8443); browser-based configuration and monitoring –
Data Export to PostgreSQL or MySQL; JSON API endpoint; automatic CSV logging –
Users and security Multi-user with role-based access; HTTPS; password protection AES-128 encrypted wireless
Inputs – 2 dry-contact inputs for switch or relay closures
Indicator – Optional maintenance LED
Enclosure Indoor Weatherproof, NEMA-rated
Operating temperature Standard indoor environment −20 °C to +70 °C (−4 °F to +158 °F)

04Installation

Power Requirements

  • Server: PoE+ (802.3at). If PoE+ isn’t available, use a PoE injector (not included).
  • Client C-AC: plug-in 110–120 VAC, or hardwired 100–240 VAC, 50/60 Hz.
  • Client C-DC: 12–24 VDC, 10 mA at 12 V. Use the supplied 12 VDC power adapter, or connect to a 12–24 VDC circuit on your equipment.

Server Installation

  • Install indoors, in a central location, as high as reasonably possible.
  • Keep the antenna away from metal surfaces.
  • Keep a line of sight to the clients where possible.
Acceptable (reduced range) Avoid where possible
Light walls (drywall, wood) Thick concrete
Some furniture Metal panels and steel structures
Glass Underground or below-grade placement
Large machinery between server and clients

Connect the server

  • Screw the 915 MHz antenna onto the gold connector.
  • Connect the server’s network jack to a PoE+ (802.3at) switch port or PoE+ injector with the supplied RJ45 cable. This cable powers the server.
Figure 1Server network jack (PoE+ power and network)

Server status LEDs

Figure 2Server front: status LEDs and antenna
LED Meaning
Red solid The server has power.
Green blinking twice per second Normal operation.
Green blinking rapidly Boot mode: the server is starting up.

Client Installation

Important

Configure the system and confirm the server and client communicate before installing.

Warning

The digital inputs accept dry-contact closures only (relay contacts or switches). Do not apply external voltage to them. See Appendix: Wiring the Client.

  • Mount near the monitored equipment. Mounting hardware is not included; use hardware suited to the surface.
  • Place the antenna away from metal and keep a line of sight to the server (see Server Installation).
  • Clients are suitable for indoor and outdoor use.

Client C-AC Wiring

Connect the AC client with the supplied power cable (110–120 VAC) or hardwire it to a 100–240 VAC supply.

  1. Route the power cable or supply wires through the cable gland labeled Power, and screw the cap tight to secure the cable and seal the enclosure.
  2. Remove the four screws holding the internal mounting plate to reach the power supply terminals.
  3. Connect the AC wires to L (live), N (neutral) and G (ground), and tighten the terminal screws.
  4. Refit the mounting plate with the four screws.
  5. Connect your equipment to the digital inputs with the supplied connector cable.
  6. Check all connections are secure before powering on.
Supplied cable wire Connection
Black Live (L)
White Neutral (N)
Green Ground (G)
Figure 3C-AC client: power, DIN.1 and DIN.2 connectors

Client C-DC Wiring

The DC client comes with a 6-conductor cable already fitted through the cable gland.

Wire Connection
Red 12–24 VDC
Black Ground (GND)
Green DIN1 A
White DIN1 C
Brown DIN2 A
Blue DIN2 C

Power the DC client: choose one

Option How to connect
A. Supplied 12 VDC power adapter Join the client’s red wire to the adapter’s + wire and the black wire to its − wire with the supplied WAGO connectors. Plug the adapter into an outlet.
B. Your equipment’s 12–24 VDC circuit Connect the red wire to +12–24 VDC and the black wire to ground (−) on the equipment. No adapter needed.

Important: make sure the supply is between 12 and 24 VDC and the polarity is correct before you power it on. Switch off the equipment’s power while you wire it.

Figure 4C-DC client: the 6-conductor cable comes through the cable gland

05Client Configuration

Setting the Client Address

  1. Power off the client.
  2. Open the enclosure with a Phillips screwdriver.
  3. Set the two-digit ID on the rotary switches: S2 = first digit, S1 = second digit. S4 sets the AES key.
  4. Close the enclosure and power on.

Example: S2 = 0 and S1 = 1 gives device ID 01.

Figure 5Rotary switches
Important

Each client must have a unique ID; duplicates cause communication conflicts. Keep a list of IDs and label each enclosure.

06Server Configuration

Finding the Server IP Address

The server’s hostname is linortek-lhm. Find its IP address in your router’s DHCP client list, with an IP scanner, or from Command Prompt or PowerShell:

ping -4 linortek-lhm
Figure 6Finding the IP address with ping
Note

This works if your PC is on the same subnet as the server, or if your network allows traffic between subnets.

Web Access and First Login

  1. Open a browser and enter the server’s IP address.
  2. Accept the security warning (the server uses a self-signed certificate).
  3. On first access, create an administrator account. The password needs at least 8 characters, with an uppercase letter, a lowercase letter, a number and a special character.
  4. Log in with your new credentials.
Figure 7Creating the administrator account

Main Page

The Main page shows the server IP address, network port, software version and number of pending commands. Once clients are added, they are listed below, where you can modify their settings, send commands or delete them.

The JSON button at the top right opens raw data for all registered clients (available once devices are added).

Figure 8Main page

Adding Client Devices

  1. On the Main page, click Add New Device.
  2. Enter the 2-digit Device ID (set on the client’s rotary switches), a nickname, and the data options you want.
  3. Click Add Device. The server starts communicating with it automatically.
Figure 9Adding a client

Data Page

The Data page shows real-time readings and the latest status of each client (green online, red offline). The table refreshes automatically; click Clear Data to empty it until new data arrives.

Figure 10Data page

Configuring a Client and Sending Commands

Click the Command button for a device:

Control What it does
Meter 1/2 control Start and stop a meter manually.
HM1/HM2 trigger mode How each meter is activated. If Ext. Power is selected and no battery is connected to the client, the memory may become corrupted.
Ext Power Deep Sleep Whether the client sleeps or stays active when external power is off. Only available with an external battery connected.
Meter 1/2 presets Enable Preset Meter and enter hours including hundredths, without a decimal point; the last two digits are the decimals. E.g. 3600 = 36.00 hours.
INIT Resets the device.
Broadcast to all devices Sends the command to every connected client at once.

Select the options and click Send Command(s).

Figure 11Client commands

User Management

On the Users page:

  • Add: click Add User, enter a username and password (same rules as above), confirm the password, check Admin if needed, and click Add User.
  • Modify: click Modify, edit the name, password or role, and click Modify User.
  • Delete: click Delete and confirm.
Role Access
Admin Full system access. An admin cannot delete or demote themselves.
User Main, Data, Users (own password only) and JSON. Cannot add or delete devices.
Figure 12Users page

Network Settings

Setting How
DHCP (automatic IP) Check Use DHCP and click Update Network.
Static IP Uncheck Use DHCP, enter the IP address, network mask and default gateway, and click Update Network.
NTP server Enter the time server (default time.nist.gov) and click Update NTP.
Time zone Select your time zone and click Update Timezone.
HTTPS certificates Certificate Mode: default or custom. Upload Certificates: .crt and .key files from your IT team. Download Cert: the current certificate. Force Renew: generate a new one. Click Update Cert Settings.
Note

After changing the IP address, reconnect using the new address.

Communications: Radio Polling and Database Export

Radio polling

Sets how often the server talks to the clients. Choose the polling mode and interval, enable automatic polling for continuous monitoring, and click Save. We recommend the default values unless you need to optimize.

Database auto export

  1. Enable Database Auto Export.
  2. Select PostgreSQL or MySQL.
  3. Enter the host IP, port, database name, username and password.
  4. Click Save.
Figure 13Communications page

Software Updates

  1. Open Software Update and click Choose File.
  2. Select the .enc update file and click Apply Update.
  3. Wait for the system to restart.
Warning

Do not power off the server during an update.

Audit Log

Records system activity and user actions for security and troubleshooting: logins and logouts, password changes, user account changes, devices added or removed, configuration changes, software updates and commands sent.

Help Page

Section Contents
Quick Tips Reminders for setup, operation and maintenance.
User Manual Click Download PDF Manual for the latest version.
Certificate Update Script Installs the security certificate automatically on Windows; run it if your network administrator requires it.
Support Documentation links and technical support contacts.

07Resetting the Server to Factory Settings

  1. Check power. With the server on PoE, check the red and green LEDs on the right side of the enclosure are both solid.
  2. Open the enclosure. Remove the four Phillips screws on the top lid and lift it carefully.
  3. Find the buttons. On the top board there are three push buttons; you’ll use Button 1 (top) and Button 2 (middle).
  4. Start the reset. Press and hold Button 1 for about 10 seconds, until the green LED blinks twice per second, then release it.
  5. Confirm. Press Button 2 once (don’t hold it). The green LED blinks rapidly for about 5 seconds, then twice per second for another 5 seconds, then stays solid.
  6. Finish. When the green LED is solid, the reset is complete. Refit the lid with the four screws.

08Troubleshooting

Problem Possible cause Solution
No data Duplicate ID Check the client’s rotary switches.
Client offline No power, weak signal, wrong AES key or wrong ID Make sure the client is powered, reposition the antennas, check the rotary switches, and check the AES key settings on the server.
Cannot log in Wrong password Have an admin reset it, or reset to factory settings.
No network connection IP address conflict Check Network Settings.

Maintenance

  • Keep the server firmware up to date.
  • Keep your client ID list up to date.
  • Inspect the server’s built-in fan and clean it periodically with a vacuum.
  • Back up the database regularly.

AAppendix: Wiring the Client

Figure 14Client digital input wiring