Why Use an Internal Time Server

01Why Use an Internal Time Server

Linortek devices work entirely inside your network and firewall. The only time they reach out to the internet is to set their clock from an NTP (time) server; by default this is time.nist.gov.

If your network has its own time server, you can point the device at it instead. The device then needs no internet access at all.

This takes two steps: find your internal time server, then enter it on the device.

02Find Your Internal Time Server

On a Windows PC on the same network:

  1. Open the Command Prompt app.
  2. Enter w32tm /query /peers and press Enter.
  3. Find the line that starts with Peer:. The name after it is your internal time server. In the example below it is LinorTekServer.LINORTEK.local.
  4. Copy the name; you enter it on the device in the next step.
Figure 1The Peer line shows the time server
Note

If the command shows an error, or the Peer is an internet server such as time.windows.com, your network may not have its own time server. Ask your IT department.

03Set the Device to Use It

  1. Log in to your Linortek device and open Settings – Time/Date.
  2. Make sure Use NTP Update is checked.
  3. In NTP Web Site, replace time.nist.gov with your internal time server, for example LinorTekServer.LINORTEK.local.
  4. Click SAVE.

Test the New Setting

  1. On the same page, change NTP Interval from 30 to 1 (minute).
  2. Check Log NTP Event and click SAVE.
  3. Wait a minute, then open the Logs page. If the device can reach your time server, you see NTP Clock Set Success! once every minute.
  4. When it works, set NTP Interval back to 30 and click SAVE, so the log doesn’t fill up. You can uncheck Log NTP Event too.
Figure 2Time/Date settings for the test (top) and the log entries (bottom)

04Troubleshooting

If you don’t see NTP Clock Set Success! in the log:

  • Restart the device, then check the Logs page again. Either unplug the power and plug it back in, or open System – Load/Reboot System and click Boot Mode. The restart takes a few seconds.
  • Check the network settings. If the device has a static IP address, check Configure – Network Config. The most common problems are a wrong subnet mask, gateway or DNS server. Ask your IT department for the right values.
  • Try the IP address. If the device can’t look up the server’s name, enter the time server’s IP address in NTP Web Site instead.
  • Check the firewall. NTP uses UDP port 123. Make sure the device is allowed to reach the time server on this port.

Still stuck? Contact Linortek tech support or call 336-485-6199.

Still stuck? Our support team can help with setup and configuration.