User Manual
eIO-RTU Remote Terminal Unit
Modules, installation, network access, I/O configuration, hour meter and bell features, automated tasks, settings and data collection for the modular DIN-rail eIO-RTU controller.
01Getting Started
The Linortek eIO-RTU is a modular, expandable DIN-rail I/O controller. It can be built into machinery, or scaled up to create or join a SCADA (Supervisory Control and Data Acquisition) system. The main unit, the EIO-CPU, is referred to as the SERVER throughout this manual.
The system is made of three kinds of module:
| Module | Role |
|---|---|
| EIO-CPU | Main unit: processor, web interface, 2 relays, 2 digital inputs and 2 analog inputs. |
| EIO-10DI | Digital input module: 10 inputs for external sensors. |
| EIO-8RL | Relay output module: 8 relays for controlling external devices. |
All modules share the same form factor and communicate with the EIO-CPU over the DIN-rail bus connectors using the CAN protocol. Adding a second EIO-10DI and EIO-8RL expands the system further.
Typical Applications
- Machinery: the EIO-CPU usually acts as a Remote Terminal Unit that monitors sensors on the machine for predictive maintenance. The machine itself is normally controlled by a PLC; the eIO-RTU can send an output signal to the PLC to adjust the machine based on sensor data.
- SCADA: the eIO-RTU collects data from sensors such as temperature, motion and alarm systems, for centralized monitoring, control and automation of a facility, at a much lower cost and with a simpler setup than large SCADA systems.
The eIO-RTU ships with one of several software versions. Sections that apply to one version only are marked (Hour Meter Software) or (Bell Software).
Limitation of Use
Unless specifically stated, Linortek products are not designed to switch line-voltage devices. To control a device that runs on line voltage, install an intermediary device such as a relay. Wiring a line-voltage device must be done by a qualified electrician, following local codes, including wire gauge and suitable housing.
Linortek can’t accept responsibility for harm to the user or third parties, or for damage to the device, caused by improper use of this product. This liability remains with the user.
IN NO EVENT WILL LINOR TECHNOLOGY BE LIABLE, WHETHER IN CONTRACT, TORT, OR OTHERWISE, FOR ANY INCIDENTAL, SPECIAL, INDIRECT, CONSEQUENTIAL OR PUNITIVE DAMAGES, INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR ANY LOSS OF USE, LOSS OF TIME, INCONVENIENCE, COMMERCIAL LOSS, OR LOST PROFITS, SAVINGS, OR REVENUES TO THE FULL EXTENT SUCH MAY BE DISCLAIMED BY LAW.
02Modules and Specifications
EIO-CPU
The heart of the system. It processes all I/O signals, communicates over the network and provides the web interface. Additional modules connect through the DIN-rail bus connector, which carries both power and data.
| Specification | EIO-CPU |
|---|---|
| Web server | Built in; all software runs on the unit |
| Relay outputs | 2 dry-contact signal relays, Form C, 1 A @ 30 VDC |
| Digital inputs | 2, 5–24 VDC, 30 mA max |
| Analog inputs | 2, 2-wire, 5 V max |
| CAN | CAN 2.0B |
| I2C | 5 V logic level |
| Voltage sensor | On board |
| Rechargeable battery | On board, keeps time while offline |
| Temperature sensor | On board |
| Power input | 12 VDC power supply, PoE, or 5 V USB-C (relays don’t switch on 5 V USB-C power) |
| Power output | 500 mA @ 12 VDC: +V on Relay 1, −V on Relay 2 |
| Enclosure | DIN-rail mount |
| Accessories | 12 VDC power supply, 1 m Cat5 network cable |
| Working temperature | 0 to +70 °C |
| Storage temperature | −40 to +125 °C |
| Humidity | 10–80%, non-condensing |
| Dimensions | 99.4 × 113 × 22.6 mm |
| Supported protocols | TLS 1.3, SMTP, SNTP, MQTT |
EIO-10DI
Adds 10 digital inputs. Each module connects to the EIO-CPU and is recognized automatically. The system supports up to 22 digital inputs: two EIO-10DI modules plus the 2 inputs on the EIO-CPU.
Digital inputs detect the on/off state of external sensors. The system can show whether an input is on or off, count events (resettable or non-resettable), and measure frequency (for example, as a tachometer) or period. Each input works in Pull-up (PU) or Isolated (ISO) mode, set with DIP switches inside the module’s enclosure. By default, 5 inputs are set to PU and 5 to ISO.
| Specification | EIO-10DI |
|---|---|
| Digital inputs | 10, 5–48 VDC, 30 mA max |
| CAN | CAN 2.0B |
| Voltage sensor | On board |
| Temperature sensor | On board |
| Power input | 12 VDC or 5 V USB-C |
| Enclosure | DIN-rail mount |
| Accessories | 12 VDC power supply |
| Working temperature | 0 to +70 °C |
| Storage temperature | −40 to +125 °C |
| Humidity | 10–80%, non-condensing |
| Dimensions | 99.4 × 113 × 22.6 mm |
EIO-8RL
Adds 8 dry-contact relay outputs. It connects to the EIO-CPU and is recognized automatically. The system supports up to 18 outputs: two EIO-8RL modules plus the 2 relays on the EIO-CPU. Relays 1 and 2 can also supply 500 mA @ 12 VDC to power external devices.
| Specification | EIO-8RL |
|---|---|
| Relay outputs | 8 dry-contact signal relays, Form A (normally open), 1 A @ 30 VDC |
| CAN | CAN 2.0B |
| Voltage sensor | On board |
| Temperature sensor | On board |
| Power input | 12 VDC or 5 V USB-C |
| Enclosure | DIN-rail mount |
| Accessories | 12 VDC power supply |
| Working temperature | 0 to +70 °C |
| Storage temperature | −40 to +125 °C |
| Humidity | 10–80%, non-condensing |
| Dimensions | 99.4 × 113 × 22.6 mm |
Hardware and software are subject to change. For new modules and features, contact your sales representative or visit linortek.com/products.
03Hardware Overview
The pictures below show each module’s terminals and front panel. Click a picture to see it full size.
EIO-CPU Terminals
| # | Terminal | Details |
|---|---|---|
| 1 | Digital inputs DIN1, DIN2 | 30 mA @ 5–24 VDC (ISO), or a simple contact closure (PU). Negative (−) to C, positive (+) to A. |
| 2 | 12V in | Powers the EIO-CPU when no I/O modules are connected (see Power Connection). |
| 3 | Analog inputs AIN1, AIN2 | 2-wire inputs, 5 V max. |
| 4 | I2C | 5 V logic-level I2C. |
| 5 | Relay output 1 (RLY1) | Dry-contact signal relay, Form C, 1 A @ 30 VDC: NO, C and NC terminals. |
| 6 | Relay output 2 (RLY2) | Same as RLY1. |
Power output
The EIO-CPU can supply 500 mA @ 12 VDC to power an external device, such as a sensor: +V is on Relay 1 and −V on Relay 2.
If I/O modules are connected to the EIO-CPU, you must power the system through the DIN-rail bus connector, which carries both power and data.
EIO-CPU Front Panel
| # | Item | Details |
|---|---|---|
| 1 | Status LEDs | Boot (green): flashes right after power-on (Bootload mode, used for software updates). Pulse (red): after about 5 seconds the Boot LED goes off and Pulse blinks once per second: Server mode, reachable on the network. Locate (blue): on when the Locate function is active. |
| 2 | Digital input 1 switch | Selects PU or ISO mode. |
| 3 | Digital input 2 switch | Selects PU or ISO mode. |
| 4 | USB-C connector | Connects the EIO-CPU to a PC for initial setup (see Finding the IP Address over USB). It also powers the EIO-CPU at 5 V, but the relays don’t switch on USB power. |
| 5 | Locate switch | Press with a paper clip to turn the blue Locate LED on or off, to find this unit among several on the same network. |
| 6 | PoE LED | Green when the EIO-CPU is connected to a PoE switch. |
| 7 | CAN LED | Green, blinking, while an I/O module communicates with the EIO-CPU over the DIN-rail bus; off otherwise. |
EIO-10DI
The digital input module adds 10 inputs. More can be added by connecting another EIO-10DI on the DIN-rail bus.
| Terminal / item | Details |
|---|---|
| Blocks 1, 2, 4, 5, 6 | Digital inputs DIN1–DIN10: 30 mA @ 5–48 VDC (ISO), or a simple contact closure (PU). |
| Block 3 | Not used. |
| Pulse LED (red) | Blinks once per second while powered. |
| CAN LED (green) | Blinking: connected to the DIN-rail bus and ready to configure. Solid: configured and running. |
| Locate LED (blue) | On while Locate is active. |
| Locate button | Press with a paper clip to turn on Locate. The module is then identified under Configure – CAN Settings. |
| USB-C connector | For factory programming; not normally used. |
EIO-8RL
The relay output module has eight normally-open dry-contact relays, RLY1–RLY8. RLY1 and RLY2 can also supply 12 VDC to drive external devices directly. More can be added by connecting another EIO-8RL on the DIN-rail bus.
| Terminal / item | Details |
|---|---|
| Blocks 1, 2 | RLY1, RLY2, with a built-in 500 mA @ 12 VDC output to power external devices without a separate supply. If not powering a device, they work as dry-contact relays like RLY3–RLY8. |
| Block 3 | Not used. |
| Blocks 4, 5, 6 | RLY3–RLY8: dry-contact signal relays, Form A, 1 A @ 30 VDC. |
| Pulse LED (red) | Blinks once per second while powered. |
| CAN LED (green) | Blinking: connected to the DIN-rail bus and ready to configure. Solid: configured and running. |
| Locate LED (blue) | On while Locate is active. |
| Locate button | Press with a paper clip to turn on Locate. The module is then identified under Configure – CAN Settings. |
| USB-C connector | For factory programming; not normally used. |
| LEDs 1–8 (red) | On while the matching relay is closed. |
04Installation
Every eIO-RTU comes with all the parts and software needed to install and run it. When it arrives, check the contents against your packing list.
Step 1: Mount the DIN Rail
- Fix the DIN rail to the panel or enclosure.
- Make sure it is level and firmly attached.
Step 2: Install the DIN-Rail Bus Connectors
- Snap the first bus connector onto the DIN rail.
- Add one more bus connector for each additional module.
- Check that all connectors are aligned and fully seated on the rail.
Step 3: Mount the Modules
All modules snap on and off the DIN rail.
- Align the module with the bus connector, with the DIN-rail hook at the bottom edge of the rail.
- Hook the module onto the rail first.
- Press down firmly until it snaps into place. You will feel the snap, and may hear it in a quiet room.
- Repeat for each additional module.
Removing a module
Insert a flathead screwdriver into the metal clip and lever it away from the rail to release the lock, then tilt the module forward and off the rail.
Step 4: Power Connection
| Option | Details |
|---|---|
| A: DIN-rail bus connector | Recommended; required with multiple modules. Connect the power supply’s positive wire (+, black without a white stripe) to the connector’s + terminal, and the negative wire (−, with a white stripe) to its − terminal. |
| B: 12V input terminal | Powers the EIO-CPU directly, without the DIN rail. Not recommended when other modules are connected. |
| C: PoE | Powers the EIO-CPU on its own from a PoE switch. Best for testing and configuration only. |
| D: 5 V USB-C | Powers the EIO-CPU on its own from a PC or USB adapter, for setup only. The relays don’t switch on 5 V. |
Do not use PoE to power the EIO-CPU together with other modules (EIO-10DI, EIO-8RL). PoE can’t supply enough power.
Step 5: Network Connection
- Plug a Cat5 (or better) Ethernet cable into the RJ45 connector on the front of the EIO-CPU.
- Connect the other end to your router or switch.
Step 6: Sensors and Devices
- Digital inputs: connect to the EIO-10DI input terminals (or DIN1/DIN2 on the EIO-CPU).
- Relay-controlled devices: connect to the EIO-8RL output terminals (or RLY1/RLY2 on the EIO-CPU).
- 0–5 V analog sensors: connect to AIN1 and AIN2 on the EIO-CPU.
Each EIO-CPU supports up to 2 digital input modules and 2 relay output modules.
Step 7: Power On and Test
Power on the system and check the LEDs on each module:
| Module | LED | Expected |
|---|---|---|
| EIO-CPU | Pulse (red) | Blinking |
| EIO-CPU | Boot (green) | Rapid blinking during boot |
| EIO-CPU | Locate (blue) | Off unless Locate is on |
| EIO-CPU | PoE (green) | Solid, only when powered by PoE |
| EIO-CPU | CAN (green) | On while modules communicate on the bus |
| EIO-10DI / EIO-8RL | Pulse (red) | Blinking |
| EIO-10DI / EIO-8RL | CAN (green) | Solid once configured |
05Accessing the EIO-CPU
Once the EIO-CPU is powered on and connected to the network, it gets an IP address automatically via DHCP. Find the IP address with one of the methods below, enter it in a web browser, and click Log In at the top right.
Username admin, password admin. With several EIO-CPUs on one network, use the Locate switch to identify each unit.
Finding the IP Address with Linortek Discoverer
Discoverer finds the EIO-CPU on your network and gives a simple way to open its web pages. It may need the Java runtime.
- If needed, install Java from java.com/en/download.
- Download Linortek Discoverer from Downloads – Support Programming.
- Unzip the download and run Linortek_Discover_desktop.exe.
- If Windows shows “Windows protected your PC”, click More info, then Run anyway.
- Click the EIO-CPU in the list to open its web pages, and log in.
The program is new and not yet known to Microsoft SmartScreen, so Windows shows a warning on first launch. The app comes from Linortek and is safe to run.
For each device, Discoverer shows:
| Column | Shows |
|---|---|
| IP Address | The device’s IP address, usually assigned by DHCP. |
| Host Name | The device’s host name. |
| MAC Address | Unique device identifier. |
| Other Info | “Blue LED” if Locate is on, product name, software revision, and port number if set. |
Finding the IP Address from the Command Prompt
If Discoverer doesn’t work, ping the SERVER by name:
- Open the Start menu, type cmd and select Command Prompt.
- Type the command below and press Enter.
- If it succeeds, the replies show the IP address. Enter it in your browser.
Finding the IP Address over USB
- Connect the EIO-CPU’s USB-C connector to your PC.
- Find the COM port number in Windows Device Manager.
- Open a terminal emulator and connect to that COM port as a serial connection.
- Type the command below. The SERVER replies with its IP address.
Connecting Directly to a PC
If you still can’t connect, or your network has no DHCP, connect the EIO-CPU directly to your PC. Unless a static IP has been set, it uses the default address 169.254.1.1.
- Connect the EIO-CPU to your computer’s Ethernet port with the supplied RJ45 cable.
- Turn off your computer’s Wi-Fi.
- Open a web browser and go to the address below.
Once logged in, you can set a permanent IP address under Configure – Network Config, then reconnect the EIO-CPU to your network and use that address.
06Initial System Configuration
Setting the Time Zone
- Go to Settings – Time/Date.
- Enter your time zone, e.g.
-5Eastern,-6Central,-7Mountain. - Check Use NTP Update.
- If you use daylight saving time, check Use Daylight Savings Time and set it for your location.
- Click Save.
An incorrect time zone gives the wrong time and can cause unexpected behavior, for example tasks running at the wrong time. See Time/Date Page for all settings.
Connecting I/O Modules
- Go to Configure – CAN Settings.
- Click the Edit icon.
- Enter a description (e.g. “Outputs”) and select the device type (EIO-8RL or EIO-10DI).
- Click Save. The device ID and CAN ID are assigned automatically, and the module shows a green online indicator when it is configured.
Assigning Inputs and Outputs
By default, DIN1, DIN2, RELAY1 and RELAY2 belong to the EIO-CPU. To use the module I/O:
- Go to Configure – Inputs/Outputs Settings.
- Check the box for each DIN or RELAY you need.
- Choose the device and I/O number for each one. For example, assign EIO-10DI input 2 to DIN2, input 5 to DIN3 and input 6 to DIN4.
The inputs and outputs then appear in this order on the In/Out page.
07Landing and Home Pages
Landing Page
Entering the IP address (and port number, if set) opens the Landing page. It shows the SERVER name, which you can change on the Network Configuration page. The page is static, with no background activity, so it is a good place to park when you are not using the SERVER but want to keep the connection open.
Click LOGIN and enter your username and password (default admin/admin). The browser keeps your credentials until it is closed. You can turn off the login requirement on the Settings page.
Landing Page (Hour Meter Software)
With the hour meter software, the Landing page also shows the data from each hour meter:
- Expandable meters with independent triggers: 2 as standard, up to 16 when you add I/O modules. Every meter in use is shown on the Landing page.
- Each meter records up to 999,999.99 hours, in 1/100-hour steps by default (1/10 can be selected on the Hours page).
- A running indicator spins while all conditions are met and the meter is counting.
Home Page
After you log in, the Home page shows system information and lets you locate the physical device.
| Item | Description |
|---|---|
| TIME | Current time and day of the week, in 12-hour (AM/PM) or 24-hour format. |
| DATE | Current date. |
| VOLTS | Voltage at the board. Useful for spotting voltage variation when the SERVER shares power with other equipment. The EIO-CPU runs on 12 VDC, PoE or 5 V USB-C; on 5 V USB-C the relays don’t switch. |
| TEMPERATURE | Board temperature in °C or °F. It is always slightly above ambient, because of the heat the SERVER itself generates. |
| LEDs | Red: system pulse; blinks about once per second while the server runs. Green: bootloader use; generally not shown. Blue: click to turn on or off. It lights on the unit itself, so you can find it among similar units (“Locate”); Discoverer also shows when it is on. |
08Relays and Inputs
In/Out Page
The Services menu changes with the SERVER’s configuration. It is where you control inputs, outputs, sensors and other special controls.
Select Services – In/Out to see the relays and inputs on one page. The EIO-CPU itself has two relays (Relay 1, Relay 2), two digital inputs (DIN1, DIN2) and two analog inputs (AN1, AN2); module I/O you assign appears here too. You can rename all of them.
Relay Control
The first section of the In/Out page lists the relays. The State LED shows whether a relay is on (green) or off (red); click it to switch the relay manually. Each relay can have a name and labels for its NO, C and NC connections. Four status LEDs show:
| LED | On when |
|---|---|
| An email is sent when the relay switches on or off. | |
| Pulse | A pulse width and multiplier (duration) are set (see Set Relay). |
| Sched. | A task on the Tasks page triggers this relay. |
| Timed | Turns red while a pulsed relay is running on its timer. |
Click the Edit icon on a relay line to open its Set Relay page.
Set Relay Page
| Field | Description |
|---|---|
| Relay Select | The relay line you clicked. |
| Name | 15 characters, letters and numbers only. This and the NO/C/NC labels can hold any identifying information. |
| Pulse Width | 0 = no timed pulse; any other number (up to 4 digits, e.g. 1234) turns the relay on for that duration. |
| Pulse Width Multiplier | Unit for the pulse width: None, mS (1/1000 s), Sec or Min. |
| Relay Type | Normal: relay on this SERVER · Latched: not currently supported · Remote: a relay on another Linortek device, over the network · Zigbee: a relay on a remote device, over RF · Normal and Remote / Normal and Zigbee: both relays · Remote BELL: a bell at a remote location (bell software only) · Normal and Remote BELL: local and remote bells (bell software only). |
| Location ID | Number of the remote location (see Remote Devices). |
| Relay at Location | Number of the relay or device at that location. |
| Send Email | Send an email when the relay turns on or off (see Email Setup). |
Inputs
The In/Out page shows a box for each input. At the top is its label, such as DIN 1 (digital) or AIN 2 (analog), which turns green when the input is enabled. Inside is the display set on the input’s settings page. A dot at the lower left shows the state of a linked relay, if any (red off, green on), and the Edit icon at the lower right opens the Set Digital Input or Set Analog Input page.
Set Digital Input Page
Digital inputs can show their data in several display types, with a name and an associated relay (green/red, and clickable to control it).
| Field | Description |
|---|---|
| Digital Input Selected | The input you are editing. |
| Name | 15 characters, letters and numbers only; shown in the bar at the top of the display. |
| Label | 7 characters; shown on the display itself. |
| Corrector | Add, subtract, multiply or divide the value before it is displayed. Up to two operations separated by a space, using +, -, * or / (e.g. *3 +2). |
| USE | Activates the input; its number turns green. Active inputs use CPU time, so turn on only the ones you need. |
| Type | State (on/off) · CounterNR (non-resettable counter) · CounterR (resettable counter) · Frequency (e.g. a tachometer; 1 Hz = 60 RPM) · Period (in milliseconds; for timing events). |
| Display | Dot (value in a colored dot, label below; good for State) · Values (value with the label below) · Meter (dial scaled by Min/Max, with colored arcs and the label inside) · VBar (vertical bar scaled by Min/Max, colored by range). |
| Relay L/T | A relay number to show and control from this display (any relay, on any input). Add L (e.g. 2L) to make the input follow the relay, or T to make the relay follow the input. |
| Command Z/N/I | Z zero the resettable counter · N normal input · I invert the input. |
| Value Min/Max | Display range, after the Corrector. A Meter can’t go past Max, so set Max to at least 1. |
| Yellow / Red / Green | Value ranges for each color, after the Corrector. For a State input, use Red 0–0, Green 1–1 and Yellow 2–2, so yellow is never used. |
Set Analog Input Page
Analog inputs use the same Name, Label, USE, Display, Relay, Value and color fields as digital inputs (the Relay field has no L/T option). The Corrector and Type fields differ:
| Field | Description |
|---|---|
| Corrector | As for digital inputs. For a thermistor, enter its values instead: T (thermistor resistance), B (beta value), R (external resistor), V (voltage), e.g. T10000 B3892 R10000 V4.77. |
| Type | Analog 1 / Analog 2: analog inputs AIN1/AIN2 · AC Current 1 / AC Current 2: AC current sensor on AIN1/AIN2 · AC Current 3: not used · Volts: voltage powering the device · Current: total current drawn by the module · Int. Temp: on-board temperature sensor · Ext. Temp / R. Humidity: temperature and % relative humidity from the AM2302 sensor (sold separately) · MMA X / MMA Y / MMA Z: accelerometer axes. |
For a Meter with Min 60 and Max 220: Green 60–180 (safe), Yellow 181–199 (warning), Red 200–220 (danger).
09Hour Meter (Hour Meter Software)
Hours Page
After wiring the SERVER to your equipment and choosing a trigger, turn on and configure the meters under Services – Hours. The page has one column per meter, with identical settings.
The hour meter software starts with 2 meters. Adding I/O modules (EIO-10DI, EIO-8RL) lets you add more, up to 16 hour meters, each with its own trigger and shown on the Landing page.
| Field | Description |
|---|---|
| Use Meter | Must be checked for the meter to run. |
| Trigger | What starts and stops counting: an INPUT, a RELAY, or the INPUT VOLTAGE (the meter runs whenever the SERVER is powered). |
| Meter Name | Identifies what is being metered. |
| Seconds/Tick | Counting resolution. Smaller numbers wear the memory faster; usually set to 2. |
| Used Endurance | The memory allows a finite number of writes and will wear out. This shows how much of it is used. Endurance in seconds = Tick × 512 × 100,000. |
| Voltage Threshold | Must be met along with the trigger for the meter to count, so it stops before a power loss can corrupt memory. Example: on a 24 V system, a 20 V threshold stops the meter as power declines. |
| Send Email / Email Count | Send an email when the meter passes this value (see Email Setup). |
| Relay Control / Relay Count | Activate a relay when the meter passes this value, e.g. to turn on a maintenance light or buzzer. |
| Preset | Set the meter to zero or any other value. |
| Push Report Interval | How often, in minutes, the hour report is sent to the Hour Collector app. Default: every minute. |
| Count Hours By | Each meter records up to 999,999.99 hours, in 1/100-hour steps by default; you can change it to 1/10. |
Email Count, Relay Count and Preset can be entered in [seconds] or (hours).
Resetting the Meter Automatically
To reset a meter at regular times, for example daily, create a task on the Tasks page with Device C set to HOURMETER, Data C set to the meter number and Action set to RESET. The example below resets meter 2 every day at 12:00 AM.
10Bells and Schedules (Bell Software)
Schedules
You can create up to 10 schedules, such as a regular schedule, teacher work days and holidays. Bell events belong to a schedule, so set up your schedules first.
- Go to Services – Schedules. A default schedule, Schedule 1, is already in use; it can’t be deleted until you add another.
- In the Add section at the bottom of the page, enter a name (15 characters max) and a description (32 characters max).
- Click Add.
Adding Bell Events
Each schedule can hold up to 500 events. Select the schedule first, then go to Services – Bells. The add section is at the bottom of the page.
| Field | Description |
|---|---|
| Name | 15 characters max, no special characters. |
| Time | 24-hour format, HH:MM:SS. |
| Date | Optional. If set, the bell rings only on this date; the days of the week are disabled and the date is shown instead. |
| Duration | A number from 1 to 99 and a unit (mS, Sec or Min). If left empty, the bell rings for 1 millisecond. |
Click Add. New events use bells 1 and 2, Monday to Friday, by default. Click a pip under a bell or day to change it: selected pips are green, others grey. Click SAVE after changing pips. Click DEL at the end of an event to delete it, or Reset to delete all events.
Downloading Bell Events
Save your events to a text file, to keep a copy or to reuse them on other schedules or devices.
- On Services – Bells, click DOWNLOAD. A new window shows your events, starting with
#Start. - Create a .txt file and paste the events into it, including
#Startat the very beginning. - Save the file.
Bell Event File Format
You can edit the events in the text file before uploading them. The file always starts with #Start, followed by one event per line, with the values separated by commas in this order:
| Value | Format |
|---|---|
| Name | Any words, 15 characters max. |
| Hour, Minute, Second | 2 digits each, 24-hour format (3 PM = 15). |
| Year, Month, Day | 2 digits each. Use 00,00,00 for an event that repeats on its days of the week. |
| Bells | 8 digits, one per bell: 1 = ring, 0 = don’t ring. For example, 11110000 rings bells 1–4. |
| Day of week | 7 digits, Sunday to Saturday: 1 = ring that day. Monday to Friday = 0111110. |
| Duration | 1 to 99. |
| Duration multiplier | Ms, Sec or Min. |
| Use | 1 = in use, 0 = not in use. |
| Once | 1 = run once only, 0 = normal schedule. |
Example: an event named Morning ringing bell 1 for 5 seconds at 7:00, Monday to Friday:
Uploading Bell Events
- Select the schedule that should use the events.
- On Services – Bells, click Upload.
- Browse to your .txt file and click Upload.
- Return to the Bells page. The events are listed, with the number of records uploaded.
11Tasks (Automatic Events)
Tasks Page
The Tasks page lists up to 64 automatic events. Each is an IF … THEN statement whose IF part can have two terms: IF a AND/OR/NOT b THEN c. Click the dot in the Use column to turn a task on (green) or off (red), and click the Edit icon to create or change it.
Set Task Page
| Field | Description |
|---|---|
| Task Select | The task line you clicked. |
| Task Name | 15 characters. |
| USE | Must be checked for the task to run. It unchecks itself if the data has an error. |
| LOG | Write to the system log every time the task runs. |
| Send an email every time the task runs. | |
| Device A / Data A | The first IF condition (see data formats). On an error, USE unchecks and the faulty field is highlighted when you click Save. |
| Logic | AND: A and B are both true · OR: A or B is true · NOT: A is true and B is not. |
| Device B / Data B | The second IF condition, in the same formats. |
| Device C / Data C | What to control (see Device C). |
| Action | ON · OFF · TGL (toggle) · RESET (reset counters). |
Data A and B Formats
| Device | Enter | Example |
|---|---|---|
| Minute | mm |
30 |
| Hour | hh (24-hour) |
14 |
| Day | dd |
01 |
| DayofWeek | Sunday = 1, Monday = 2 … Saturday = 7, Weekday = 8, Weekend = 9 | 8 |
| Time | hh:mm, 24-hour with leading zeros; seconds are ignored |
07:30 |
| Date | yy/mm/dd with leading zeros |
20/01/10 (January 10, 2020) |
| Relay | Relay number and + (on) or - (off) |
01+ |
| Button | + (on) or - (off) |
+ |
| Flag | Flag number, with + for on (optional) or - for off |
3+ |
| Temp | >, = or < and a value, always in °C |
>40 |
| Volts | >, = or < and a value |
<10 |
| Analog | Input number, >, = or <, and a value |
2<123 |
| Digital | Input number, type, >, = or <, and a value. Types (case-sensitive): S state · C non-resettable counter · c resettable counter · F frequency · P period (1/1000 s) |
1F>7500 |
Device C and Data C
| Device C | Data C |
|---|---|
| RELAY | Relays on this SERVER, up to four, separated by commas, e.g. 1,2,3,4. |
| FLAG | One of 8 storage flags that can be turned on or off, to build more complex tasks. |
| REMOTE | A relay on another Linortek device: remote unit number,remote relay, e.g. 3,5. Set up the remote units on the Remote Devices page. |
| COUNTER | Add a count to digital input counter 1 or 2. |
| BLUE LED | Turns on the blue LED. No data needed. |
| SEND EMAIL | Sends an email. Leave empty for the full JSON report; if Device A or B is an analog or digital input, enter Short for a short input report. Works with digital and analog inputs only. |
| NOTIFY | Writes the current data to the log. Analog inputs only. |
| DELAY | Delays turning a relay on: relay,seconds, e.g. 1,180. |
| HOURMETER | Meter number to reset (use with Action RESET), e.g. 1. |
| SEND UART | Not supported by the current software. |
| SEND MQTT | Leave empty for the full JSON report. To publish a single value under its own topic (e.g. lt1000/<MAC>/relay/1), enter relay/1 or relay/2, digital/1 or digital/2, hourmeter/1 to hourmeter/16, or analog/1 to analog/4. |
The example below is a typical task built this way.
Logs
The Logs page keeps over 10,000 entries for actions taken by the SERVER or by users. Each entry has a reference number, time and date, followed by the event. The log refreshes automatically.
- Use the checkboxes above the log to show or hide entries from each source.
- Use the date window to filter by date.
- Click DOWNLOAD below the log to save it as a TXT or CSV file.
12Settings
User and Admin Credentials Page
Under Settings you can set up to 3 users. Only User 1 is active by default.
| Field | Description |
|---|---|
| User Name / Password | Defaults: admin/admin, user2/user2 and user3/user3. Passwords are never displayed. |
| Active | Must be checked for the user to log in. User 1 can’t be deactivated. |
| Admin | Only admin users can save changes on most pages, which protects the SERVER from unauthorized changes. |
| Timeout | Not available at this time. |
Passwords are limited to 13 characters. If you set a longer password, you won’t be able to log in to that account.
Time/Date Page
| Field | Description |
|---|---|
| Time | hh:mm:ss, always standard time. |
| Date | yy/mm/dd. |
| Time Zone | Offset from UTC, e.g. -5 for EST, -8 for PST. Add :mm for part-hour zones, e.g. 5:30. |
| Use MIL Time | 24-hour format. |
| Use NTP Update | Synchronize the time with an NTP server. |
| Use Daylight Savings Time | Adjust the time automatically for daylight saving (not accurate in all time zones). |
| DST starts/ends | DST dates, if different from the default (North and South America). |
| Daily time correction | Correction to apply if the SERVER can’t reach an NTP server. |
| NTP Web Site | The NTP server used for updates. |
| NTP Interval | Minutes between updates. |
| Log NTP Event | Log every NTP update (normally not logged; useful for troubleshooting). |
Settings Page
| Setting | Description |
|---|---|
| Use System emails | Enables additional email messages. |
| Use Audio File System | Depends on the application; not needed for the hour meter software. |
| Use AM2302 | Use the AM2302 temperature/humidity sensor (sold separately). |
| Java Report | Send data to the Hour Collector app over Ethernet (hour meter software only). |
| Require Login | If unchecked, anyone can access the SERVER without credentials. |
| WiFi Report | Data transfer over Wi-Fi (for iTrixx Wi-Fi devices). |
| Active Landing page | Shows additional information on the Landing page. |
| Invert Relay Control | Swaps relay states between NO and NC without rewiring. |
| Use Serial Comm | Not supported. |
| Use Fahrenheit | Fahrenheit instead of Celsius. |
| Use RESTful Authentication | Require a username and password for RESTful access. |
| Extend Relay Range | Enables 8 relays. |
| Use Relay Radio Buttons | Turning one relay on turns all others off. |
| SSL Port No. | Not used here; set the HTTPS port on the Network Configuration page. |
| UART Usage | Depends on the application; not needed for the hour meter software. |
| Discovery Port | UDP port for Discoverer messages, 30303 by default. If you change it, change it in Discoverer too. |
| Select theme | Red, green or blue. |
| Upload / Download | Save the configuration file, or load a saved one. It covers relays, inputs, network settings and tasks. |
| Change Logo | Replace the Linortek logo with your own (.png, 60 kB max). |
13Configure
Network Configuration Page
Incorrect settings can make the SERVER lose its network connection. If that happens, you may need to restore the defaults.
| Field | Description |
|---|---|
| MAC Address | Unique address set at assembly; can’t be changed. |
| Host Name | The SERVER’s name on the network. It may appear in your router’s lease list, and is shown on the Home page and in Discoverer. |
| Port Number | Needed for internet access. Default: 80 (443 for HTTPS). |
| Enable DHCP | On by default. Uncheck to set a static IP address. |
| IP Address | Usually only the last group of numbers changes. Reserve the address on your router and make sure no other device uses it. |
| Gateway | Usually your router, the access point to your ISP. |
| Subnet Mask | Leave at 255.255.255.0. |
| Primary / Secondary DNS | DNS servers. |
HTTPS
To use HTTPS, set the port number to 443 and save. From then on, open the web pages at https://<IP address>:443. To choose which certificate is used, see HTTPS Config.
Access from outside your network
To reach the SERVER remotely, set a static IP address and port number here, then port forward that address on your router, so the router sends incoming traffic to the SERVER (see your router’s manual). For a stable internet address, see Dynamic DNS.
HTTPS Config Page
Under Configure – HTTPS Config you choose the certificate the SERVER uses for HTTPS connections (see Network Configuration to turn HTTPS on).
| Option | Description |
|---|---|
| Use built-in certificate | Default. The connection is encrypted, but browsers show a security warning because the certificate isn’t issued for your network; accept it to continue. |
| Use uploaded certificate | Uses a certificate you upload, for example one from your IT team, if your network requires it. |
To upload a certificate:
- Under Select new certificate, click Browse and choose the certificate file.
- Click Upload.
- Select Use uploaded certificate.
Dynamic DNS Page
Dynamic DNS, together with port forwarding on your router, gives global access to a SERVER behind a NAT router or firewall. Set a static IP address and port on the Network Configuration page first. The only supported service is DynDNS.
| Field | Description |
|---|---|
| Use DDNS | Enables the service. |
| DDNS Service | DynDNS. |
| User Name / Password | Your DynDNS account. |
| Host | The host name registered with DynDNS for this SERVER. |
Email Setup Page
Set up the email account the SERVER uses to send messages from relays, tasks and hour meters.
| Field | Description |
|---|---|
| SMTP Server | Your outgoing mail server. Your mail provider publishes this and the other settings. |
| Port | The SMTP server’s port. |
| Use SSL | 2048-bit SSL. Check only for port 465. |
| User Name / Password | Your email account. |
| To Address | The recipient. |
| Subject | Email subject line. |
CC and BCC are not supported yet.
MQTT Setup Page
MQTT (MQ Telemetry Transport) is a lightweight messaging protocol that lets devices share data and send commands to each other using very little bandwidth.
| Field | Description |
|---|---|
| MQTT Server | IP address of the computer running the MQTT broker, e.g. 192.168.1.10. |
| Port | The broker’s port; 1883 by default. |
| Username / Password | Optional; only needed if the broker requires a password. |
| Topic | The topic (channel) to use. Enter an existing topic name, or a new one to create it. Only devices connected to a topic see its messages. |
| Client ID | Required. The name the SERVER uses on the broker, e.g. “Device A”. It is separate from any username. |
IP Range Configuration Page
Reserved for future use: it will limit access to a range of IP addresses.
Remote Devices Page
Lets the SERVER control relays on up to 8 other Linortek devices (peer-to-peer), from a task or a relay set as Remote.
| Field | Description |
|---|---|
| Device Name | A name for your reference. |
| IP Address | The remote device’s IP address, including the port number. |
| User Name / Password | The remote device’s login (Basic Authentication). |
Incorrect settings make the SERVER lose its remote connections.
14System
Load/Reboot System Page
Under System – Load/Reboot System you can update the software or restore the factory defaults.
Reset to Factory Default
Resetting restores the default login (admin/admin), for example if you forgot the password.
From the web pages
- Open System – Load/Reboot System.
- Check Restore Default Values and click Boot Mode.
- The reset is complete when the red LED blinks once per second again.
On the EIO-CPU
- Power cycle the EIO-CPU: disconnect its power, then reconnect it.
- Within the first 5 seconds, while the green Boot LED is flashing (Bootload mode), press and hold the Locate switch with a paper clip.
- Keep holding until the red LED is solid, then release.
Update Software
The SERVER leaves the factory with the latest software. When a new version is released:
- Download the .img file from the Linortek Downloads page.
- Open System – Load/Reboot System, check Update Software and click Boot Mode.
- In Discoverer, find the SERVER in Bootloader state and click its IP address. The upload page opens.
- Click Browse, select the .img file and click Upload.
- When “Done!!” appears, click the link to return to the login page.
The software version is shown at the bottom of every page.
15Data Collection and Integration
Once wired and configured, the SERVER reports its data over your network. Any computer on the same network can collect it with the free Linortek apps, or through MQTT, the RESTful API, JSON or Microsoft Excel.
Hour Collector App (Hour Meter Software)
A free app for Linortek hour meters. It finds the SERVER automatically, gives quick access to it like Discoverer, and updates every two minutes by default (the interval can be changed in the app). It requires Java.
- Download Hour Collector (Downloads – Support Programming)
- Linortek HourMeter Collector App Setting Instruction (Downloads – Documentation)
DataCollector Pro App
A desktop app that listens for UDP broadcasts from Linortek hour meters and logs the data to a .csv file. It can also collect data manually: useful for port-forwarded hour meters, since it can read their XML pages over the internet. It also reads the Wi-Fi mini via REST or an MQTT broker.
- Download DataCollector App Pro (Downloads – Support Programming, Special Programs)
- Linortek Data Collector App Setting Instruction (Downloads – Documentation)
RESTful API and XML
Read data from the SERVER or control its inputs and outputs directly over HTTP.
MQTT
The SERVER publishes to the topic below, where xxxxxxxxxxxx is its MAC address in lower case. It sends a single JSON payload to the broker set on the MQTT Setup page, at QoS 0, on the interval you set. Tasks can also publish single values (see SEND MQTT).
For details, see the iTrixx WFMN MQTT – Product Documentation on the Downloads – Documentation page.
JSON
The SERVER also provides a JSON report on port 30000, over HTTP only (not HTTPS):
Still stuck? Our support team can help with setup and configuration.